Accessories; Humidifier; Sequence Of Operation; Continuous Fan - Carrier PF4MNX Installation Instructions Manual

Fan coil units
Table of Contents

Advertisement

PF4MNX: Installation Instructions
Install traps in the condensate lines as close to the coil as possible.
(Fig.
18). Make sure that the outlet of each trap is below its connection
to the condensate pan to prevent condensate from overflowing the drain
pan. Prime all traps, test for leaks, and insulate traps if located above a
living area. Condensate drain lines should be pitched downward at a
minimum slope of 1" (25 mm) for every 10' (3 m) of length. Consult
local codes for additional restrictions or precautions.

Accessories

Humidifier

Connect the humidifier and humidistat to the fan coil unit as shown in
Fig. 19
and
Fig.
20. The cooling lockout relay is optional.
PRIMARY TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF
SUFFICIENT DEPTH.
STANDARD P-TRAPS ARE
NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED
CONDENSATE TRAP)
Fig. 18 – Condensate Drain

Sequence of Operation

Continuous Fan

Thermostat closes the R to G connection. G energizes the fan relay on
the PCB which completes the circuit to the indoor blower motor. When
G is de-energized, there is a 90-second delay before the relay opens.
THERMOSTAT
RED
R
GRY
G
BRN
C
WHT
W
2
WHT
BLU
E
L
O
Y
FAN HUMIDIFIER
115V
M
Fig. 19 – Wiring Layout of Humidifier to Heat Pump
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
FILTER
ACCESS
PANEL
SECONDARY DRAIN WITH
APPROPRIATE TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP)
FAN COIL
HEAT PUMP
(CONTROL)
(CONTROL)
R
R
G
C
C
W
2
W
3
VIO
E
W
2
O
Y
RELAY
HUMIDISTAT
THERMOSTAT
R
G
W
Y
FAN HUMIDIFIER
115V
M
Fig. 20 – Wiring Layout of Humidifier to Fan Coil

Cooling Mode

Thermostat energizes R to G, R to Y, and R to O (heat pump only). G
energizes the fan relay on the PCB which completes the circuit to the
indoor blower motor. When G is de-energized, there is a 90-second delay
A03003
before the fan relay opens.

Heat Pump Heating with Auxiliary Electric Heat

Thermostat energizes R to G, R to Y, and R to W connections. G
energizes the fan relay on the PCB which completes the circuit to the
indoor blower motor. W energizes the electric heat relay(s) which
completes the circuit to the heater element(s). When W is de-energized,
the electric heat relay(s) open, turning off the heater elements. When G
is de-energized there is a 90-second delay before the fan relay opens.

Electric Heat or Emergency Heat Mode

Thermostat closes R to W connection. W energizes the electric heat
relay(s) which completes the circuit to the heater element(s). Blower
motor is energized through the normally-closed contacts on the fan relay.
When W is de-energized, the electric heat relay(s) opens.

Start-up Procedures

Refer to outdoor unit Installation Instructions for system start-up
instructions and refrigerant charging method details.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit performance
and/or product damage.
Never operate unit without a filter. Factory authorized filter kits may be
used when locating the filter inside the unit. For those applications
where access to an internal filter is impractical, a field-supplied filter
must be installed in the return air duct system.
A95294
10
FAN COIL
(CONTROL)
RED
R
GRY
G
WHT
W
2
WHT
BLU
W
3
VIO
E
BRN
C
HUMIDISTAT
with Electric Heat
CAUTION
!
AIR COND.
C
Y
A95295

Advertisement

Table of Contents
loading

Table of Contents