Dimplex LI 1422C Installation And Operating Instruction page 19

Air-to-water heat pump for indoor installation
Table of Contents

Advertisement

LI 1422C - 1826C
8.1
Type of defrosting
8.2
Condensate tray frost protection/water in device is protected from freezing
8.3
Max. operating overpressure (heat sink)
2 5
9
Heat output / COP
9.1
Heat output / coefficient of performance (COP)
10 Cooling capacity / coefficient of performance (COP)
10.1 Cooling capacity / coefficient of performance (COP)
1. For air temperatures between -22 °C and -5 °C, flow temperature increasing from 45 °C to 60 °C.
2. This data indicates the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and
the regulation should be taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for care, commissioning and operation can be found
in the relevant sections of the installation and operation instructions. The specified values have the following meaning, e.g. A2/W35: Heat source temperature 2 °C and heating
water flow temperature 35 °C.
3. Tonal component according to DIN 45681 Table 1 is indoors ≤ 2 dB / outdoors ≤ 1 dB
4. Sound measurement takes place with two 90° bends and weather protection grills on the intake and air outlet.
5. The heat output and COP is reduced by approx. 5% in lower operation
6. The specified sound pressure level represents the free sound area level. The measured value can vary by up to 16 dB(A), depending on the installation location.
7. Note that additional space is required for pipe connections, operation and maintenance.
8. see CE declaration of conformity
9. The heat circulating pump and the heat pump manager must always be ready for operation.
10.Special operation, normal operation above 5 °C outside temperature 1 compressor operation
www.dimplex.de
at A-7 / W35
kW / ---
at A2 / W35
kW / ---
at A7 / W35
kW / ---
2 3
at A27 / W18
kW / ---
at A27 / W7
kW / ---
at A35 / W18
kW / ---
at A35 / W7
kW / ---
452170.66.01-EN · FD 0303
Reverse cycle
9
Yes
bar
3.0
EN 14511
1
2
7.5 / 3.3
13.9 / 3.1
9.4 / 4.1
15.9 / 3.7
11.7 / 5.0
(20.9 / 4.7)
EN 14511
1
2
10.4 / 4.0
21.0 / 3.6
6.8 / 2.7
16.0 / 2.8
10.3 / 4.0
19.3 / 2.9
6.5 / 2.3
14.8 / 2.3
English
Reverse cycle
Yes
3.0
EN 14511
1
2
9.8 / 3.4
18.3 / 3.2
11.3 / 3.9
18.6 / 3.7
10
14.2 / 4.8
(21.3 / 4.2)
EN 14511
1
2
10.9 / 3.3
19.2 / 2.6
7.9 / 3.5
16.5 / 2.3
9.5 / 2.5
17.7 / 2.1
7.0 / 1.9
14.9 / 1.9
EN-17
10

Advertisement