Water Heater Installation Checklist - Bradford White EF120T4003NA3 Service Manual

Commercial ultra high efficiency models with direct spark ignition and icon control system
Hide thumbs Also See for EF120T4003NA3:
Table of Contents

Advertisement

Water Heater Installation Checklist

Product Handling
Electrical Requirements
Venting Requirements
Gas Requirements
Condensate Requirements
Service/Mechanical Room
3 in. Vent Pipe
Max. Intake Length
Max. Exhaust Length
4 in. Vent Pipe
Max. Intake Length
Max. Exhaust Length
6 in. Vent Pipe
Max. Intake Length
Max. Exhaust Length
The 120T models are NOT approved for 2 diameter vent pipe. Venting with 2 pipe may result in damage to the water
heater or cause an unsafe condition. DO NOT use 2 in vent or air intake pipe.
Note: Each 90° elbow is equivalent to 5 ft. (1.5 m) of straight pipe.
Note: Each 45° elbow is equivalent to 2 ½ ft. (0.8 m) of straight pipe.
Carefully uncrate the heater. Move in place with a hand truck (DO NOT use the venting
pipes for handles).
Make sure there is 120 volts line voltage. Line voltage must be properly polarized.
Adequate ground supplied to the heater.
All venting must stay within the required lengths and diameter (see table below). Proper
support of the venting pipe is required (every 5 ft. vertical and 3 ft. horizontal).
Termination must be located to prevent re-circulation of flue gases. Use factory supplied
intake and exhaust terminations.
Refer to tab
Condensate line needs to slope to a drain at a minimum of 1/4 in. per ft. Make sure the
condensate line does not have the potential to freeze. If using more than one heater
and using a common condensate line, make sure the condensate line is properly sized.
Provide adequate space for servicing heater. Leave room to get to the bottom safety
switch as well as enough overhead room to remove the anode rods for servicing (18 in.
minimum).
Vent Tables
Power Direct Vent and Power Vent Maximum Vent Length
(Combined Maximum Length for Intake and Exhaust)
Air intake CANNOT exceed exhaust
by more than 30 ft
120T-400-3N(A) 399,999 BTU/hr
Power Direct Vent
65 ft.
65 ft.
Power Direct Vent
100 ft.
100 ft.
Power Direct Vent
120 ft.
120 ft.
Power Vent
Power Direct Vent
N/A
65 ft.
Power Vent
Power Direct Vent
N/A
100 ft.
Power Vent
Power Direct Vent
N/A
120 ft.
WARNING
47
120T-500-3N(A) 499,000 BTU/hr
Power Vent
65 ft.
65 ft.
Power Vent
100 ft.
100 ft.
Power Vent
120 ft.
120 ft.
N/A
65 ft.
N/A
100 ft.
N/A
120 ft.
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents