Type of
Switch No.
Switch
1
2
SW5
3,4,5
ZRP100–140: No function
6
ZRP200/250: Model select
1
2
3
Max Hz setting (cooling)
SW7*
4
4
Max Hz setting (heating)
5
Breaker capacity setting *
6
1
SW8
2
3
DIP
1
switch
SW9
2
3,4
1
ZRP100–140: No function
2
ZRP200/250: Model select
3
4
5
SW6
6
7
8
*
2
'Power failure automatic recovery' can be set by either remote controller or this DIP SW. If one of them is set to ON, 'Auto
recovery' activates. Please set "Auto recovery" basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
*
3
SW7-1 is setting change over of Demand/Low noise. It is effective only in case of external input.
(Local wiring is necessary. Refer to the next page: Special function)
*
4
Please do not use SW7-3 to 7-6 usually. Trouble might be caused by the usage condition.
*
5
With this switch setting, the capacity decreases up to 30% under peak load condition. Thus this setting is recommended
only for Air to water purposes.
*
6
ZRP100–140 only.
*
7
SW5-1 to 5: Function switch
OCH645
Function
No function
Power failure
automatic recovery *
2
No function
Mode select *
3
No function
Max Hz (cooling) o 0.8
Max Hz (heating) o 0.8
5
Defrost setting
No function
No function
No function
Fan motor switch *
6
Function switch
No function
Model select
Action by the switch operation
ON
Auto recovery
No auto recovery
Following SW5-6 reference
Demand function
Low noise mode
Decrease capacity
For high humidity
High static pressure
Valid
MODEL
SW6
MODEL
ON
100Y
100V
OFF
1 2 3
4
4 5
6
7
8
ON
125V
125Y
OFF
1 2 3
4
5
6
7 8
ON
140V
140Y
OFF
1 2 3
4
5
6
7
8
MODEL
SW5-6
SW6
ON
ON
200Y
OFF
OFF
1 2 3
4
4 5
6
7
8
1 2 3 4 5 6
ON
ON
250Y
OFF
OFF
1 2 3
4
4 5
6
7
8
1 2 3 4 5 6
70
Effective timing
OFF
When power supply ON
Normal
Normal
Normal
When power supply ON
Normal
Normal
When power supply ON
Normal
SW6
ON
OFF
1 2 3
4 5
4
6
7
8
ON
OFF
1 2 3
4 5
4
6
7
8
ON
OFF
1 2 3
4 5
4
6
7
8
7
*
The black square (
) indicates a switch position.
Always
Always
Always