Mitsubishi Electric PUHZ-ZRP100VKA3 Service Manual page 30

Hide thumbs Also See for PUHZ-ZRP100VKA3:
Table of Contents

Advertisement

10-2-3. Test run for wireless remote controller (Type C)
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M".
1 Turn on the main power to the unit.
2 Press the
button twice continuously.
TEST RUN
(Start this operation from the status of remote controller display
turned off.)
A
TEST RUN
and current operation mode are displayed.
MODE
3 Press the
(
check whether cool air blows out from the unit.
4 Press the
(
MODE
check whether warm air blows out from the unit.
FAN
5 Press the
button and check whether strong air blows out
from the unit.
VANE
6 Press the
button and check whether the auto vane operates
properly.
7 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps 2 to 7.
• It is not possible to run in FAN, DRY or AUTO mode.
10-2-4. Test run for wireless remote controller <PAR-SL100A-E>
1. Press the
button 1 to stop the air conditioner.
button 3 to disable it (
2. Press the
button 2 for 5 seconds.
comes on and the unit enters the service mode.
3. Press the
button 2.
B comes on and the unit enters the test run mode.
4. Press the following buttons to start the test run.
5. Stop the test run.
Press the
button 1 to stop the test run.
After 2 hours, the stop signal is transmitted.
OCH645
) button to activate
mode, then
COOL
) button to activate
mode, then
HEAT
is on), press the
is off).
.
7
MODE
3,4
CHECK LOUVER
TEST RUN
2
3
30
TEST RUN
TEMP
ON/OFF
FAN
AUTO STOP
5
AUTO START
VANE
6
h
min
SET
RESET
CLOCK
B
A
1
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents