Follow the instructions below to assemble batteries/single units:
 Open and remove the front door to facilitate handling
 Remove the two internal "A" and "B" panels, see Fig. 2.
 Remove the left and right side panels to facilitate battery installation and connection. THE REAR PANEL
OF THE BATTERY CABINET MUST NEVER BE REMOVED.
 Remove the front locking brackets by the various shelves. Position the batteries on each shelf as per Fig.
3. Use the provided tool to facilitate battery insertion on the shelves (see chapter "Battery assembly
accessory").
 Reposition all front locking brackets.
 Connect the batteries and switch with the supplied cables as per Fig. 4, Fig. 5 or Fig. 6 (20 batteries
version) or as per Fig. 7 or Fig. 8 (40 batteries version) complying with cable numbering.
ATTENTION: the supplied clear plastic guards must be mounted on the Q1 battery cabinet switch
Front locking
bracket
Assemble the two 125A NH00 fuses (or the two 63A NH000 fuses) F1 - F3 using the supplied handle (20
batteries) (see Fig. 4, Fig. 5 and Fig. 6).
Assemble the three 125A NH00 fuses (or the three 63 NH000 fuses) F1 - F2 - F3 using the supplied
handle (40 batteries) (see Fig. 7 and Fig. 8).
The wiring nuts and bolts must be tightened as per the table below
- ENGLISH -
65Ah
Side locking
bracket
Tightening torque
Battery terminals 5 - 7 Nm
Switch terminals 14 Nm
40Ah / 40+40Ah
Front locking
bracket
Fig. 3
8
Side locking
bracket

Advertisement