BATTERY CABINET - UPS INTERCONNECTIONS

ATTENTION: before making connections, make sure that the UPS is completely switched off and that there
is no dangerous voltage on the UPS connection terminals.
Check that the battery switch Q1 is open
Open and remove the front door to facilitate handling
Remove the two internal "A" and "B" panels, see Fig. 2.
Connect wires (connection cables not supplied) from the battery cabinet to the UPS terminals (see
Fig. 11).
Connect as follows:
1. PE ground connection (yellow-green wire) to be connected first
+
-
2. "
" and "
" pole connections
For dimensions of connection cables between the battery cabinet and UPS, refer to the UPS manual.
- ENGLISH -
Q1
Fig. 11
15