Operating And Installation Instructions - Siemens WS 5 Series Operating And Installation Instructions

Ultrasonic heat, cooling meter and combined heat/cooling meters
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 10
s
en
Operating and
Installation Instructions
Note: In the following text, the term meter refers to both
the heating meter and the cooling meter unless they are
otherwise differentiated.
1.
General
1.1
Use
The WS.5.. is used as a meter for heating or cooling consump-
tion measurement in systems with water.
The meter consists of a high-tech plastic volume measurement
unit, two temperature sensors connected in a fixed position and
an electronic unit that calculates the energy consumption from
the volume and temperature difference.
The meter combines modern microcomputer technology with
innovative ultrasonic measuring technology for which no me-
chanically moving parts are necessary.
This technology is thus wear free, robust and largely mainte-
nance free. High precision and long-term stability guarantee
precise and equitable cost accounts.
Note: The meter cannot be opened without damaging
the security seal.
1.2
General notes
The meter left the factory in a faultless condition where safety
is concerned. The manufacturer will provide additional tech-
nical support on request. Calibration relevant security seals on
the meter must not be damaged or removed. Otherwise, the
warranty and calibration validity of the meter will no longer
apply.
Keep the packaging so that you can transport the meter in
its original packaging following expiry of the calibration va-
lidity.
Lay all cables at a minimum distance of 500 mm to high
voltage and high frequency cables.
A relative humidity of <93% at 25 °C is permissible (without
condensation).
Avoid cavitation in the whole system due to overpressure
i.e. at least 1 bar at qp and approx. 2 bar at qs (applies for
approx. 80 °C).
2.
Safety Information
The meters may only be used in building service
engineering plants and only for the applications de-
scribed.
The meter is designed in accordance with the guide-
lines of the environment categories M1+E1 and must
be fitted in line with these regulations.
The local regulations (installation etc.) must be ad-
hered to.
The operating conditions according to the type plate
must be complied with during use. Non-compliance
can result in hazardous situations and the expiry of all
claims arising from liability for defects as well as liabil-
ity on the basis of any expressly granted guarantees.
Do not under any circumstances carrying out welding,
drilling or soldering work close to the meter.
The meter is only suitable for circulating water in
heating systems.
The meter is not suitable for drinking water.
Siemens Building Technologies
Ultrasonic heat, cooling meter and combined
heat/cooling meters WS.5..
3.
To install the meter proceed as follows:
Requirements for circulating water (CEN/TR 16911:
2016).
Only personnel, trained in the installation and opera-
tion of meters in heating and cooling systems, may
install and remove the meter.
Only install or remove the meter when the pipes are
pressure-less.
After installing the meter, check the leak-tightness of
the system.
Guarantee and calibration validity will lapse if the
calibration relevant security seal is broken.
Only clean the meter from outside with a soft, lightly
wetted cloth. Do not use any spirit or cleaning solvent.
As far as disposal is concerned, the meter is a waste
electronic appliance in the sense of European Di-
rective and it must not be disposed of as domestic
waste.
-
Dispose of the meter through the channels pro-
vided for this purpose.
-
Respect the local and currently valid legislation.
-
Dispose of used batteries at the collection points
provided for them.
-
You can find additional documents about the
disposal
http://www.siemens.com/bt/download.
The meter contains lithium batteries. Do not dispose of
the meter and the batteries with domestic waste.
Observe the local stipulations and laws on disposal.
You can return the lithium batteries to the manufactur-
er for appropriate disposal following use. When ship-
ping please observe legal regulations, in particular,
those governing the labelling and packaging of haz-
ardous goods.
Do not open the batteries. Do not bring batteries into
contact with water or expose to temperatures above
80 °C.
The meter does not have any lightning protection.
Ensure lightning protection via the in-house installa-
tion.
Installation
Determine the place of installation in line with the inscrip-
tion on the meter.
Note: At a heating meter
the flow sensor cold side is equivalent to return
. The mounting place of the flow sensor hot
side is equivalent to flow
CE2U5372xx
CE2U5372xx
22.06.2020
Translation
WS.5..
of
products
the mounting place of
.
22.06.2020