Domestic Hot Water Circuit - Baxi 24 Combi Installation And Service Manual

High-efficiency wall-hung condensing gas boiler
Hide thumbs Also See for 24 Combi:
Table of Contents

Advertisement

5 Before installation
Fig.29
Circuit plan
G
B
C
D
E
38
600 Combi 2
5.7.2
A
B
C
A
D
E
F
G
F
All DHW circuits, connections, fittings, etc. should be fully in accordance
with relevant standards and water supply regulations.
Your attention is drawn to:
PN-0000350
for GB: Guidance G17 to G24 and recommendation R17 to R24 of the
Water Regulations Guide.
for IE: the current edition of IS 813 Domestic Gas Installations.
The Water Regulations recommendations for England and Wales prohibits
backflow from appliances into the wholesome water supply due to thermal
expansion. However this type of instantaneous combination boiler, with
less than 15 litres of stored capacity, does not require any backflow pre­
vention device as any thermal expansion is accommodated within the ap­
pliance. It is possible in certain circumstances that other cold water de­
mands (e.g. washing machines, flushing of WCs) may affect the DHW
function of the boiler. In these instances the fitting of a backflow prevention
device and expansion vessel is recommended.
The boiler's maximum working mains pressure is 8 bar, therefore all pipe­
work, connections, fittings, etc. should be suitable for pressures in excess
of 8 bar. A pressure reducing valve must be fitted for pressures in excess
of 8 bar. The manufacturer of any outlet fittings, such as a shower valve,
may require a lower maximum pressure. The pressure reduction must take
account of all fittings connected to the DHW system.

Domestic hot water circuit

Boiler
Expansion vessel
Check valve
Pressure reducer
Stop tap
To hot tap
Other tap outlets
Important
In instances where the mains water supply incorporates a non-re­
turn backflow prevention device, or any other device that includes
one*, it is possible for a build-up of pressure to occur. This may re­
sult in damage to the boiler and other appliances. To prevent
damage to the boiler it is strongly recommended that a suitable
mini expansion vessel is fitted on the mains water inlet between
the boiler and the non-return device.
*(The manufacturer of the device should be consulted if there is
any doubt regarding the presence of a non-return feature).
Even in circumstances where a non-return device is not fitted any
future modifications to the mains inlet (e.g. fitting of a water meter)
should be considered and an expansion vessel fitted. Baxi cannot
accept any responsibility for damage to the boiler if these
recommendations are not followed.