2.2.8 CONFIGURATION Screen

The Configuration screen can be used to set specific parameters and control functions.
NOTICE! Parameter ID's shown in 'red' text will only be accessible with the Engineer
log-in code.
Fig.10 – Control System Configuration screen
Configuration - Filling
ID
Title
P101
Fill Pressure
P102
Fill Hysteresis
P103
Fill Pump Run Period
P104
Level Sensor Delay
P105
Fill Start Delay Period
P106
Fill Warning Delay Period
P107
Manual Fill Control
Configuration – Pump Control
ID
Title
P201
Control Type
P202
Flow Setpoint
P203
Differential Pressure Setpoint
P204
Low Flow %
P205
Low DP Hys
P206
Low Flow/DP Delay
P207
Minimum Pump Speed
P211
Over-pressure Setpoint
P212
Over-pressure Action
P213
Start-up Speed
P214
Start-up Period
P215
Loop Refresh Period
P216
Maximum Control Pressure
P217
DP Setpoint – Max Cooling
Mode
P216
Cooling Fan Run On Period
CDU Operating & Maintenance Guide
Neptune DWC RM100 in-rack Coolant Distribution Unit
Description
Start threshold for fill pump
Stop hysteresis for fill pump
Time for level sensor to make, or fill pressure to
be satisfied, prior to alarm (when unit is on-line)
Level Senor response time, prior to alarm
Delay prior to pump start after initiate signal
Delay prior to 'check make-up' alarm activated
Select Manual or Automatic Fill pump control
0 = Manual; 1 = Automatic
Description
Select pump speed controlled by flow or DP
Set the required Secondary flow rate
Set the required Secondary differential
pressure (DP)
Low flow alarm threshold (% of flow setpoint)
Low DP alarm hysteresis
Time delay prior to low Flow/DP alarm
Set minimum pump running speed
Maximum system pressure, prior to alarm
Alarm only, or shutdown & alarm
Initial pump start fixed speed (0 = Auto)
Initial start speed hold period, prior control
loop taking over
Scan period for pump speed control loop
Maximum pump speed control loop pressure
DP Setpoint used when operating in Max
Cooling mode
The period of time the fan will run on for after
the unit is switched to standby
16
Page
Default
Range
Unit
0.8
0.3 to 1.0
Bar
0.2
0.1 to 0.5
Bar
1
1 to 15
min
1
1 to 6
secs
10
1 to 60
secs
5
0 to 60
secs
1
0 or 1
-
Default
Range
Unit
Flow
Flow or DP
-
50
5 to 130
l/m
0.3
0.1 to 4.0
Bar
90
50 to 95
%
0.5
0.1 to 3
bar
100
1 to 300
secs
10
10 to 70
%
6.0
2.0 to 7.0
Bar
Alarm
Alarm or
-
Alarm+S/D
0
0 to 100
%
0
0 to 100
secs
10
1 to 120
secs
4.0
1.0 to 8.0
Bar
2.5
1 to 5.0
Bar
10
0 to 60
mins