Mass Notification Features

Notes:
• MN System works on Standard and Hi-speed Noti•Fire•Net
• A total of 15 ONYXWorks workstations may participate in paging on a mass notification system.
1.2 Mass Notification Features
MN events can be programmed as higher or lower than fire events, based on risk analysis.
MN alarms suppress fire alarm events when MN is the highest priority.
MN alarms are generated locally
– by an ACU, LOC, or CCS page.
– by manual activation of a UL-approved switch or button device installed for initiating MN alarms. A Listed UL2017 initiating
switch/device is required.
MN events generate messages over Noti•Fire•Net to MN-mapped nodes.
Programmable using VeriFire Tools.
Automatic activation of Special Function Zone ZF20 to signal MN alarm.
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
ACU
NFS-320/SYS
(NFS2-3030 and
DVC)
NFS2-640
CCS
(NCA-2 and DVC,
NCA-2
or ONYXWorks)
Figure 1.1 Block Diagram Example of an MN System
LOC
LOC
(DVC-RPU and
(DVC-RPU and
LCD-160)
LCD-160)
Noti•Fire•Net
LOC
(DVC-RPU and
ACU
LCD-160)
(NCA-2 and
DVC)
LOC
(DVC-RPU and
LCD-160)
LOC
LOC
(DVC-RPU and
(NCA-2 or NFS2-
LCD-160)
3030 and DVC)