3.1 Overview

When a system is configured for both fire and MN protection, programming determines which events always have the highest priority -
MN or fire. If MN is programmed as the highest priority at the fire panels and network annunciators, fire events are suppressed when
MN alarms are active. For the DVC, PAM programming for the MN Active Tone will suppress the activation of fire sequences and
pages.
Special Function Zones and Type Codes separate MN alarm, supervisory and trouble messages from fire messages, so that each can be
correctly prioritized and displayed by the system. Mapping links nodes that will communicate with each other regarding MN events.
This chapter describes the special MN programming (needed in addition to fire programming) for an MN system.
NOTE: Program all panels, DVCs, network annunciators and workstations in a system with the same mass notification priority settings.
The established priorities must be consistent throughout a system.
NOTE: All fire panel and display nodes must be programmed with DCC disabled. DVC nodes must be programmed as described in this
chapter.

3.2 Programming Steps

This section lists the MN programming steps required, and provides reference to the appropriate programming, detailed in Section 3.3,
for each station, panel, or network annunciator. These steps must be followed if the system is set up for MN and fire, or MN only.
Refer also to Section 4.3, "Output Event Suppression", on page 40. This section presents basic principles for suppression.
3.2.1 ACU
An ACU is comprised of an NFS2-3030 and a DVC, or an NCA-2 and a DVC
1 Set the mass notification priority.
2 Set the DCC field.
3 Set the MN Control Field to ACU.
4 Map to MN nodes.
5 Program with MN type IDs.
6 Program with MN Special Function Zones.
* NFS2-3030 must be in network display mode to function as part of an ACU.
1 Set the MN mode, enable paging levels.
2 Enter associated NFS2-3030/NCA-2 node number.
3 Program input categories and priorities.
4 Create and program an MN Active Tone.
5 Create and program a Fire Active Tone (when Fire is the highest priority).
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019

Section 3: Programming

ACU Programming Steps
NFS2-3030*/NCA-2
Field
DVC
Refer to:
page 19
page 18
page 35
page 23, page 23
page 24
page 25
page 21
page 19
page 21,page 22
page 25
page 29