Programming
Table 3.2 lists and describes MN control module and panel bell circuit Type IDs.
Type Code
MNS
GENERAL
MNS
CONTROL
MNS
STROBE
MNS
SPEAKER
MNS RELAY
Activations will generate mass notification events locally and over a network. Trouble conditions at these points will generate MN trou-
bles.
3.3.6 Special Function Zones
The MN Special Function Zones in Table 3.3 below activate when an MN alarm, supervisory, or trouble event occurs.
NOTE: Use ZF20 in the map of an LED annunciator programmed with a "monitor" mode as a dedicated MN alarm indicator.
Special
Function
Name
Code
ZF20
MN Alarm Zone Activates for local events and network ZF20 activations when an MN alarm is present in the system. It
ZF21
MN Supervisory
Zone
ZF22
MN Trouble
Zone
The MN Special Function Zones are available as indicated in Table 3.4.
3.3.7 MN Active Tone
When MN has the highest priority in a network and the DVC is operating in Mass Notification mode, it must be programmed in VeriFire
Tools to generate an "MN Active Tone". This programming is required for two reasons:
It generates an audible reminder every 30 seconds that MN has control of the system and that fire signals may be suppressed if MN
is the highest priority.
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Point
Switch
Type
Silenceable
Inhibit
NAC
N
NAC
N
NAC
N
NAC
N
Relay
N
Table 3.2 MN Control Type IDs
suppresses fire protection when MN is prioritized as higher than fire (see "Output Event Suppression" on
page 40). It is sent out to the network, and each networked panel will check the ZF20's source against its
table of mapped MN nodes. If the source has a match in the table, fire protection will be suppressed in the
panel that made the match. Logic equations will be activated.
Activates for local events when there is an MN supervisory in the system.
Activates for local events when an MN trouble occurs.
Table 3.3 MN Special Function Zones
NFS2-3030
NCA-2
NFS2-640/NFS-320/SYS
DVC
ONYXWorks Workstation
Table 3.4 MN Special Function Zone Availability
Point Characteristics
Walk
Test
N
N
Mass notification supervised output.
N
N
Mass notification supervised NAC.
N
N
Mass notification supervised NAC.
N
N
Mass notification supervised NAC for speaker
circuits.
N
N
Mass notification relay output.
Description
ZF20
ZF21
Device Function
ZF22
Programming
25