Dometic FreshJet3 Series Installation Manual page 18

Climate control rooftop air conditioner
Hide thumbs Also See for FreshJet3 Series:
Table of Contents

Advertisement

Available languages

Available languages

Installation
7 .3 .1 Locating the DIP switches
18 Electronic control box DIP switch location
DIP switch
q
w
The electronic control box is located at the return air
opening on the base of the AC and the DIP switches are
visible through the opening.
The DIP switches are set to the Off position when
shipped from the factory, except for heat pump models.
Placing the switch in the On position selects that option.
7 .3 .2 Setting the DIP switches
This section describes the appropriate electronic
control box DIP switch settings. The position should be
set to the appropriate On or Off position based on the
equipment options installed by the RV manufacturer.
19 DIP switch board
On or closed switch position
q
Off or open switch position
w
If your RV has more than one electronic control box
installed, configure each electronic control box with the
appropriate DIP switch settings.
If necessary, press each switch On (Closed) or Off (Open)
according to the following configuration table.
18
w w
q q
ON
1 2 3 4 5 6 7 8 9 10
Electronic control box
q q
w
w
Rooftop air conditioner (air distribution box, wall thermostat controls)
DIP switch setting configuration
DIP location
1
Zone 2
2
Zone 3
3
Zone 4
4
Stage
5
Furnace
1
6
Gen Start
1
7
Heat Strip
1
8
Heat Pump
2
9
Dehumidify
1
10 120 ohm
CAN
termination
resistor
1,3
Climate Module Communication (CMC) only
1
2
Current or CMC communication only
ON by default for RV-C
3
Description
Each thermostat can have up to four
zones. If only one rooftop component is
installed, it becomes zone 1 by default
and DIP switch settings for zones 2, 3, or
4 are not required.
If more than one rooftop component is
installed, assign each rooftop component
a separate zone (2 through 4). Each
rooftop component must have a different
zone setting.
For applications requiring two
rooftop components to work together in
the same zone, set the Stage DIP switch
to the On position.
Otherwise, leave in the Off position.
If a Furnace/hydronic heating
system has been connected to this
rooftop component, set the Furnace DIP
switch to the On position.
Otherwise, leave in the Off position.
To configure the Automatic Generator
Start for a new installation, refer to
"Routing an automatic generator start
(AGS) feature via RV-C (optional)" on
page 14. Leave this DIP switch in
the Off position, unless it is required for
backwards compatibility using the CMC
protocol.
Leave this DIP switch in the Off position,
unless it is required for backwards
compatibility using the CMC protocol.
For Heat Pump models, this DIP switch is
set in the On position from the factory.
For non-Heat Pump models, change this
DIP switch to the Off position.
The Dehumidify is not used on this
rooftop component.
Leave this DIP switch in the Off position,
unless it is required for backwards
compatibility using CMC protocol.
This DIP switch is in the On position from
the factory to enable RV-C (CAN BUS)
communication. Only the first and last
devices on the CAN bus should enable
the 120 ohm termination resistor.
EN