Introduction
Type of Device
Other Modules
ECS Modules
Wireless
12
Model
5824 Serial/Parallel
Allows a printer to be attached for the system for on-site event logging. Four maximum
Printer Interface Module
per system.
5815XL (Rev H or above)
Allows up to 127 SD devices to be added to the system. The number of 5815XL
SLC Expander
modules that can be added to the system is limited only by the maximum number of
SBUS devices. However the maximum point count is limited to 254 per panel. Supports
SD protocol devices only.
6815 SLC Expander
Supports System Sensor Devices (IDP or SK) only. Each 6815 supports up to 159 IDP
or SK sensors and 159 IDP or SK modules. Maximum point count is 300 per panel.
RPS-1000 (Rev F or
Provides additional power, six Flexput circuits,
higher) Intelligent Power
and two Form C relays.
Supply
5496 (Rev F or above)
Add 4 Notification/Auxiliary power circuits with
NAC Expander
each 5496 Intelligent Power Module
RA-2000 Remote LCD
4x 40 Remote LCD annunciator, can be used in any combination, up to a total of 16
Annunciator
devices on one panel.
RA-100 Remote LCD
4 x 20 Remote LCD annunciator, can be used in any combination, up to a total of 16
Annunciator
devices on one panel.
RA-1000 Remote LCD
4 x 20 Remote LCD annunciator, can be used in any combination, up to a total of 16
Annunciator
devices on one panel.
5860TG and 5860TR
trim ring kits for surface mounting the RA-1000 annunciator. 5860TG is gray; 5860TR is
Trim Ring Kits
red.
5865-3 and 5865-4 LED
LED annunciator can display up to 30 LEDs (15
Annunciator
red and 15 yellow). 5865-4 has key switches for
silence and reset, and a system trouble LED.
5880 (Rev C or above)
Driver for up to 40 LEDs. Interfaces with
LED I/O Module
customized annunciator boards. In addition the
5880 has eight generic switch input points.
5883 General Purpose
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883
Relay Module
modules can be used with each 5880 module.
SK-NIC
Network Interface Card
ECS-NVCM
Network Voice Control Module
ECS-VCM
Voice Control Module
ECS-SW24
24 switch expander
ECS-50W
50 watt audio amplifier
ECS125W
125 watt audio amplifier
ECS-CE4
Provides 4 additional audio circuits for the ECS-
50W or ECS-125W.
ECS-RVM
Remote Voice Module
ECS-DUAL50W
Dual Channel amplifier
ECS-50WBU
Backup daughter card
ECS-INT50W
50 wall internal amplifier
ECS-LOC
Local Operating Console
WIDP-WGI/WSK-WGI
Wireless Gateway
WIDP-PHOTO/WSK-
Wireless Photoelectric Smoke Detector
PHOTO
Wireless multi-criteria photoelectric smoke
WIDP-ACCLIMATE
detector
WIDP-HEAT-ROR/WSK-
Wireless Rate of Rise Heat Detector
HEAT-ROR
WIDP-HEAT/WSK-HEAT
Wireless 135° Fixed Heat Detector
WIDP-MONITOR/WSK-
Wireless Addressable Monitor Module
MONITOR
WIDP-RELAY/WSK-
Wireless Addressable Relay Module
REALY
B210W
6" wireless base
Table 1.1 IFP-300 Compatible Products (Continued)
Description
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Compatible Products
RPS-1000 and 5496 modules can be
used in any combination, up to a total
of 16 on one system.
5865-3, 5865-4, and 5880 can be
used in any combination, up to a total
of eight devices on one panel.
Refer to LS10172-001SK-E
Refer to the ECS Series Installation
Manual P/N 151455for more
information on these accessories.
Refer to the SWIFT Wireless
Installation Manual
P/N LS10036-000FH-E for more
information on these accessories.