Connect the red wire from the battery harness to the positive (+) side of battery #1.
4.7.12 Calculating Current Draw and Standby Battery
This section helps determine the current draw and standby battery needs for your installation (18 AH maximum will fit in cabinet). Complete
the remaining instructions in Table 4.6.
Batteries larger than 18 AH will not fit in the main control cabinet, and must be housed in the RBB Accessory Battery Cabinet. The system
supports a maximum of 35 AH.
ECS-DUAL50W 25V
ECS-DUAL50W 70.7V
ECS-50WBU
A
Current Subtotals:
Notification Devices
B
Current Subtotals:
C
Total current rating of all devices in system (Line B) X 0.001
D
Number of standby hours (24 or 60 for NFPA 72)
E
Multiply line C (standby current) and D:
F
Alarm sounding period in hours (For example, 5 minutes = 0.0833 hours):
G
Multiply line C (alarm current) and F:
H
Add lines E and G (AH = Ampere Hours):

4.8 Installing the ECS-50WBU

The ECS-50WBU provides backup capability when operating the ECS-DUAL50W in the 100 watt with backup mode for both single and
dual channel setups. The ECS-50WBU mounts on the ECS-DUAL50W board on the standoffs provided.
54
Figure 4.64 Battery Connection to ECS-DUAL50W
No. of
Device
Devices
1
1
1
Refer to device manual for number of devices and current ratings.
Table 4.6 Current Draw ECS-DUAL50W
Current Per Device
Standby:
110 mA 110 mA
Alarm:
Standby:
110 mA
Alarm:
Standby:
40 mA
Alarm:
110 mA
Total standby AH
Total alarm AH
Total AH required
ECS Series Manual — P/N 151455:H 2/15/2022
Installing the ECS-50WBU
Standby
Alarm
Current
Current
1.2 A
1.2 A
110 mA
1.4 A
40 mA
110 MA
mA
mA
A
H
AH
AH
1.4A
mA
mA
A
H
AH