5. After the Test Run is successfully completed, and you
confirm that all checks points in List of Checks to Perform
have PASSED, do the following:
• Using remote control, return unit to normal operating
temperature.
• Using insulation tape, wrap the indoor refrigerant pipe
connections that you left uncovered during the indoor
unit installation process.
9.3
If ambient temperature is below 16°C
(60°F)
You can't use the remote controller to turn on the COOL
function when the ambient temperature is below 16°C. In
this instance, you can use the MANUAL CONTROL button
to test the COOL function.
1. Lift the front panel of the indoor unit, and raise it until it
clicks in place.
2. The MANUAL CONTROL button is located on the right-
hand side of the display box. Press it two times to select
the COOL function.
3. Perform Test Run as normal.
Manual control
button
AUTO COOL
Page 55

Advertisement

Table of Contents
loading