Note:
1) If the displayed power factor is not 1, please calculate the specification of power according
to the phase angle error.
2) [1P] 0.09kW~1000kW
3) [3P3W] 0.15kW~1732kW
4) [3P4W] 0.27kW~3000kW
3.2 Apparent power
Accuracy
Range
Resolution
15Hz~40Hz
40Hz~70Hz
Power factor: 1
Power factor: 1
±(2.0%+5)
60.00kVA
0.01kVA
600.0kVA
0.1kVA
±(2.5%+5)
±(1.7%+5)
1000kVA
1kVA
Note:
1) If the displayed power factor is not 1, please calculate the specification of power according
to the phase angle error.
2) [1P] 0.09kVA~1000kVA
3) [3P3W] 0.15kVA~1732kVA
4) [3P4W] 0.27kVA~3000kVA
3.3 Reactive power
Accuracy
Range
Resolution
15Hz~40Hz
40Hz~70Hz
Power factor: 1
Power factor: 1
±(2.5%+5)
60.00kVAr
0.01kVAr
600.0kVAr
±(3.0%+5)
0.1kVAr
±(2.0%+5)
1000kVAr
1kVAr
Note:
1) If the displayed power factor is not 1, please calculate the specification of power according
to the phase angle error.
2) [1P] 0.09kVAr~1000kVAr
3) [3P3W] 0.15kVAr~1732kVAr
4) [3P4W] 0.27kVAr~3000kVAr
3.4 Power factor
Accuracy
Range
Resolution
15Hz~1000Hz
Calculate the specification
-1~ 1
0.001
of power factor according
to the phase angle error
29
UT219P User Manual
Overload
protection
70Hz~1000Hz
Power factor: 1
1000A AC
1000Vrms
±(2.5%+5)
Overload
protection
70Hz~1000Hz
Power factor: 1
1000A AC
1000Vrms
±(3.0%+5)
Overload
Remark
protection
Min. measured
1000A AC
voltage: 30V
Max. measured
1000Vrms
current: 10A
UT219P User Manual
3.5 Phase angle
Accuracy
Range
Resolution
15Hz
40Hz
~
~
40Hz
70Hz
-180° (advance)
0.1°
±5°
±3°
~179.9° (delay)
Note:
1. The null-position cross phase difference between current and voltage waveforms is positive
if current lags behind voltage; negative if current is ahead of voltage.
2. An error of 2° is added if the measured conductor is not placed at the center of the clamp jaws.
4. Harmonic analysis
Function
Harmonic order
1
2~6
RMS of harmonic
7~8
of each order
9~10
11~15
16~30
30~40
Note:
1) Minimum measured voltage is 30V, minimum measured current: >10% of current range.
2) THD-F and THD-R are displayed on the LCD.
3) Harmonic analysis is recorded in the clamp, and can be displayed and viewed on mobile
APP via Bluetooth module.
4) If fundamental frequency is 100Hz, the harmonic order reaches 40.
If fundamental frequency is >100Hz, the harmonic order reaches 15.
5. Frequency
Range
Resolution
15Hz~1000Hz
0.1Hz
Note:
Minimum measured voltage is 30V, minimum measured current: >5% of current range.
6. Phase detection
Range
Frequency
Function
Phase Detect
80V~1000V
40Hz~80Hz
Note:
The LCD shows "1 2 3" to indicate positive phase sequence or "3 2 1" to indicate negative one.
The LCD shows "— — — —" to indicate phase loss or unmeasurable.
Overload
Remark
protection
70Hz
Min.
~
1000Hz
measured
1000A AC
voltage: 30V
Max.
1000Vrms
±5°
measured
current: 10A
Accuracy
Overload protection
15Hz~400Hz
±(3.0%+10)
±(3.5%+10)
1000A AC
±(4.5%+10)
1000Vrms
±(5.0%+10)
±(7.0%+10)
±(10.0%+10)
±(20.0%+10)
Overload
Accuracy
protection
15Hz~1000Hz
1000A AC
1000Vrms
±(0.3%+3)
Overload protection
1000Vrms
30