SEQUENCE OF OPERATIONS – ELIWELL CONTROLLER

SEQUENCE OF OPERATIONS - ELIWELL CONTROLLER

The warmer operates based on the air temperature measured by the probe located at the return air.
ON
COMPONENT
OPERATION
Heater turns on
when the air
temperature at the
HEATER
probe is above the
sum of the set point
+ 4
The Blower turns
BLOWER
on when the unit
is powered on.
The light will turn on
when the down
button is
LIGHT
pressed (or when the
door is opened with
solid doors)
14
CONTROLLER
ACTION
The Heater Contact is
energized
(RTN400 - Terminal
#10 and #11)
The Blower is wired to
constant power
(RTN400 - Terminal #4
and #5)
The Light Contact is
energized
(RTN400 - Terminal
#13 and #14)
Condition
Cabinet Temp > Set point + 4
Cabinet Temperature <= Set point - 4
OFF
OPERATION
Heater turns off
when the air
temperature at
probe is equal to
or less than the
set point
The Blower turns
off when the unit is
unplugged or put
into standby.
The light will turn
off when the down
button is
pressed (or when the
door is closed with
solid doors)
ON
OFF
Victory
Victory
CONTROLLER
ACTION
The Heater Contact is de-
energized
(RTN400 - Terminal
#10 and #11)
The Blower is wired to
constant power
RTN400 - Terminal #4
and #5)
The Light Contact is de-
energized
(RTN400 - Terminal
#13 and #14)
ON
ON or OFF
OFF
ON or OFF
Rev. 01/23