Figure 27 Connection Example 3 (2U De Connections In The Same Rack) - Fujitsu ETERNUS DX100 S4 Site Planning Manual

Hybrid storage systems
Hide thumbs Also See for ETERNUS DX100 S4:
Table of Contents

Advertisement

2.
Rack Installation Specifications
Rack Installation Requirements
Installing 2U DEs in the Same Rack (When Two Controllers Are Installed)
This section describes a connection configuration in which all of the enclosures are installed in the same rack.
The following figure shows an example when one controller enclosure (2U) and ten drive enclosures (2U) are
installed in a rack.
For this type of configuration, the length of cables that are provided with the drive enclosures is not enough to
connect the enclosures. Obtaining extra extension cables for reverse cabling to connect the controller enclosure
to the last drive enclosure is required.

Figure 27 Connection Example 3 (2U DE Connections in the Same Rack)

DE#0A (2U)
DE#09 (2U)
DE#08 (2U)
DE#07 (2U)
DE#06 (2U)
DE#05 (2U)
DE#04 (2U)
DE#03 (2U)
DE#02 (2U)
DE#01 (2U)
Cables that are supplied as standard
0.75m
Extension cables
2.5m
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide
CE
Copyright 2021 FUJITSU LIMITED
50
P3AM-7632-18ENZ0