Installation Checklist - Rheem GHE119SS Use & Care Manual

Commercial high efficiency water heater
Hide thumbs Also See for GHE119SS:
Table of Contents

Advertisement

A. Water Heater Location
Close to area of vent.
Indoors and protected from freezing temperatures.
P roper clearance from combustible surfaces
observed and water heater is not installed on a
carpeted floor.
A ir supply free of corrosive elements and flammable
vapors.
P rovisions made to protect area from water
damage.
Sufficient room to service the heater.
B. Water Supply
Water heater completely filled with water.
Water heater and piping air vented.
Water connections tight and free of leaks.
C. Gas Supply
G as line equipped with shut-off valve, union, and
sediment trap/drip leg.
Approved pipe joint compound used.
Minimum pipe size of 3/4"; NO flex pipe.
R ecommended a minimum of 10" WC inlet
pressure for natural gas.
S oap and water solution used to check all
connections and fittings for possible gas leak.
Gas company inspected installation (if required).
Measure the combustion (CO2%) level.
Based on a 0.60 Specific Gravity Natural Gas; If 1.5 Specific Gravity L.P. Gas is used, multiply capacity by 0.63
Nominal
Internal
Iron Pipe Size,
Diameter
Inches
Inches
3/4
.824
1
1.049
1 1/4
1.380
1 1/2
1.610
2
2.067
2 1/2
2.469
3
3.068
4
4.026
For maximum pipe capacity for installations in Canada, refer to CAN/CSA B149.1. For natural gas, refer to Tables
A.1 through A.17. For propane (LP) gas, refer to Tables B.1 through B.12.
Installation Check List
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of
0.5 psig or Less and a Pressure Drop of 0.3 Inch Water Column
10
20
30
278
190
152
520
350
285
1,050
730
590
1,600
1,100
890
3,050
2,100
1,650
4,800
3,300
2,700
8,500
5,900
4,700
17,500
12,000
9,700
D. Relief Valve
Discharge line run to open drain.
Discharge line protected from freezing.
E. Venting
A ll pipe connections are secure (at blower, vent
terminals and for each pipe joint connection), and
all pipes properly supported.
V ent terminals mounted properly in allowed
locations, with proper clearances .
F. Condensate
Condensate trap installed and primed.
Condensate neutralizer installed (if required).
G. Wiring
Correct power supply (120 VAC).
Electrical connections are tight.
W ater heater is properly grounded with proper
polarity.
NOTE: Each water heater should have its own
regulator located a minimum of 8' from unit.
TABLE 2
For U.S. Installations
Length of Pipe, Feet
40
50
60
70
130
115
105
96
245
215
195
180
500
440
400
370
760
670
610
560
1,450
1,270
1,150
1,050
2,300
2,000
1,850
1,700
1,600
4,100
3,600
3,250
3,000
2,800
8,300
7,400
6,800
6,200
5,800
31
80
90
100
125
150
90
84
79
72
170
160
150
130
120
350
320
305
275
250
530
490
460
410
380
990
930
870
780
710
1,500
1,400
1,250
1,130
2,600
2,500
2,200
2,000
5,400
5,100
4,500
4,100
175
200
64
59
55
110
100
225
210
350
320
650
610
1,050
980
1,850
1,700
3,800
3,500