Vitocrossal 200 CI2 Installation

System Layout 2

V
itocrossal 200, CI2 with...
- DHW storage tank
- 3 zone circuits
- 3 heating circuits with a mixing valve
Legend
Vitocrossal 200, CI2 boiler
A
B
Outdoor temperature sensor !
C
Low temperature heating circuit
D
Zone circuit
Zone pump
E
Mixing valve temperature sensor ?
F
G
Mixing valve with actuator
Domestic hot water storage tank
H
I
DHW tank temperature sensor %
Expansion tank
J
Boiler pump/system pump
K
DHW pump PI
L
Low loss header
M
N
System supply temperature sensor TSI
O
DHW recirculation pump
Installation of different heating circuits...
3 zone circuits (radiator heating circuit)
3 low-temp. circuits (under floor heating circuit with
3-way mixing valve)
DHW production with DHW recirculation
The 3-way mixing valve control, to achieve the low-
temperature level of the under floor heating circuit,
an accessory kit for a heating circuit with mixing valve
is required.
IMPORTANT
System separation is required of underfloor heating
systems employing non-oxygen diffusion barrier tubing.
All components on the secondary side of the heat
exchanger must be made of corrosion-resistant materials.
System Layout
41