Configure Communications Port Seabus (Address 7200) - Siemens ISGS Operator's Manual

Intelligent switchgear system
Hide thumbs Also See for ISGS:
Table of Contents

Advertisement

periods, or the like. Use the ft.nctions in address block 7100
to switch between prmary and alternate relay parameter
sets.
Configuration of the front port (RS-232) and SEAbus
(rea~
port (RS-485) is fol.J"ld l.J"lder address block 7200.
3.12.3
Parameter
Set (Address 7100)
Use this address block to display the active relay parameter
set, switch to the altemate set, and copy parameters
between parameter set address locations. The
displa~d
parameter set (as indicated by an "A" or
·s·
next to the
parameter block
runbe~
is not necessarily the active
parameter set. The parameter value can be changed for
each parameter, but you must
go
to the 7101 subaddress
location to see which parameter set is active, or subaddress
7103 to change to the desired active parameter set. The
available operations are listed
n
Table 3.32. The flow chart
n
Figure 3.8 illustrates how to use the operations in Table
3.32. To make parameter changes, you must first enter the
password.
If you only want to review present settings, the
password steps 4 and 5 are not necessary.
Protective functions for which altemate parameter sets are
available are indicated in Table 3.3.
Perform parameter changes using steps 1-9 of the standard
operation sequence, Table
3.4.
Address 7101 displays the
currently active parameter set, and address 7103 is used to
change from one parameter set to the other.
Subaddress
Parameter
Description
7101
Active Set
Displays active
paameter set
(AO'
8)
7103
Activation
Activates the other
para11eter set
7104
Copy
Copies the
detau
t
parameter set to set
A
7105
Copy
Copies the defaut
para11eterset to set
8
7106
Copy
Copies paameter
set A to set 8
7107
Copy
Copies parameter
set 8 to set A
Table 3.32
Parameter Set Conf1gurat1on, Mapr Block 7100
Siemens Energy & Automation,
Inc.
3
Ogeration
reB>FiOM' -
-
-
---1
1
, - -
--E----,..---
1
I
L,----r---r-"~
I
l
-
Parameter Edt
Buffer
l _
_
_
_
_
_
__
_
_
l
Figure
3.8.
Altering and Activating Parameter Sets
3.12.4 Configure Communications Port
SEAbus (Address 7200)
I
I
I
I
I
Use this address block to set the local and remote port
baud rates, allow remote communication event functions,
allow remote parameter set changes, and set the relay local
address. The available operations and parameters are listed
in Table
3.33.
To make parameter changes, you must first
enter the password. If you only want to review present set-
tings, the password step is not
necessary.
Perform parameter changes using steps 1-9 ofthe standard
operation sequence, Table 3 .4.
33