Carrier Aquazone 50PTH024 Installation, Start-Up And Service Instructions Manual page 46

Two-stage water source heat pumps with puron refrigerant
Table of Contents

Advertisement

Table 22 — 50PT 070 Typical Unit Operating Pressures and Temperatures (Part Load)
ENTERING
WATER
MODEL
WATER
FLOW
TEMP (°F)
(GPM/TON)
30
40
50
60
50PT 070
Part Load
70
80
90
100
NOTE(S):
a. These operating temperatures and pressure charts show approximate temperatures and pressures for a unit on good repair. The values shown are
meant as a guide only and should not be used to estimate system charge.
b. This chart assumes rated air flow and 80°F db/67°F wb entering air temperature in cooling, 70°F db entering air temperature in heating.
c. Heating data at entering fluid temperatures below 50°F assumes the use of antifreeze. As a result of continuing research and development, speci-
fication are subject to change without notice.
LEGEND
DB — Dry Bulb
WB — Wet Bulb
— No operation in this temperature range.
Table 23 — 50PT 070 Typical Unit Operating Pressures and Temperatures (Full Load)
ENTERING
WATER
MODEL
WATER
FLOW
TEMP (°F)
(GPM/TON)
30
40
50
60
50PT 070
Full Load
70
80
90
100
NOTE(S):
a. These operating temperatures and pressure charts show approximate temperatures and pressures for a unit on good repair. The values shown are
meant as a guide only and should not be used to estimate system charge.
b. This chart assumes rated air flow and 80°F db/67°F wb entering air temperature in cooling, 70°F db entering air temperature in heating.
c. Heating data at entering fluid temperatures below 50°F assumes the use of antifreeze. As a result of continuing research and development, speci-
fication are subject to change without notice.
LEGEND
DB — Dry Bulb
WB — Wet Bulb
— No operation in this temperature range.
COOLING
Suction
Discharge
Pressure
Pressure
(PSIG)
(PSIG)
6
9
6
120-136
197-227
9
119-135
176-206
6
122-138
229-259
9
121-137
207-237
6
124-140
264-294
9
123-139
241-271
6
126-142
303-333
9
125-141
278-308
6
128-144
346-376
9
127-143
321-351
6
131-147
393-423
9
130-146
366-396
6
133-149
443-473
9
132-148
416-446
COOLING
Suction
Discharge
Pressure
Pressure
(PSIG)
(PSIG)
6
10
6
120-136
209-233
10
119-135
182-206
6
122-138
241-265
10
120-136
212-236
6
124-140
276-300
10
122-138
245-269
6
126-142
315-339
10
124-140
282-306
6
127-143
357-381
10
126-142
323-347
6
129-145
403-427
10
128-144
369-393
6
10
129-145
418-442
Water
Air Temp
Suction
Temp
Drop
Pressure
Rise (°F)
(°F) DB
(PSIG)
62-82
68-88
17-19
22-26
74-94
11-13
22-26
82-102
16-18
21-25
88-108
11-13
22-26
98-118
16-18
21-25
102-122
10-12
21-25
116-136
15-17
20-24
118-138
10-12
21-25
135-155
15-17
20-24
136-156
10-12
20-24
157-177
15-17
19-23
156-176
10-12
20-24
181-201
14-16
19-23
9-11
19-23
Water
Air Temp
Suction
Temp
Drop
Pressure
Rise (°F)
(°F) DB
(PSIG)
65-75
69-79
18-20
21-25
77-87
11-13
22-26
83-93
18-20
21-25
91-101
11-13
21-25
99-109
17-19
20-24
107-117
10-12
21-25
116-126
17-19
20-24
123-133
10-12
20-24
136-146
17-19
19-23
142-152
10-12
20-24
158-168
17-19
19-23
163-173
9-11
19-23
182-192
10-12
19-23
46
a,b,c
HEATING
Discharge
Water
Air Temp.
Pressure
Temp.
Drop (°F)
(PSIG)
Rise (°F)
326-346
8-9
19-23
334-354
4-5
21-25
341-361
9-10
22-26
351-371
5-6
23-27
357-377
11-12
24-28
369-389
6-7
27-31
347-394
12-13
28-32
390-410
7-8
30-34
393-413
14-15
31-35
412-432
8-9
33-37
413-433
16-17
34-38
436-456
9-10
37-41
434-454
18-19
37-41
461-481
10-11
41-45
a,b,c
HEATING
Discharge
Water
Air Temp.
Pressure
Temp.
Drop (°F)
(PSIG)
Rise (°F)
280-304
6-7
18-22
285-309
3-4
19-23
294-318
7-8
20-24
301-325
4-5
21-25
309-333
8-9
23-27
316-340
5-6
24-28
322-346
10-11
26-30
330-354
6-7
27-31
336-360
11-12
28-32
346-370
7-8
30-34
351-375
13-14
31-35
363-387
8-9
33-37
367-391
14-15
34-38
380-404
9-10
37-41