UPM STATUS LED — BLINK CODES
1
High Pressure Fault
2
Low Pressure Fault
3
Condenser Freeze Condition
4
Condensate Overflow Fault
5
Brown Out Fault
6
Evaporator Freeze Condition
Factory Wiring
Field Wiring
STANDARD COMPONENTS LEGEND
AUX
— Auxiliary Relay (For Loop Pump, Etc.)
BM
— Blower Motor
CBR
— 24V Circuit Breaker
CC
— Compressor Contactor
CS
— Condensate Sensor (In Drain Pan)
EMS
— Energy Management System Relay
FS
— Freeze Sensor
HPS
— High Pressure Switch
LED
— Unit Status LED
LPS
— Low Pressure Switch
PM
— Phase Monitor
RV
— Reversing Valve (Heat Pumps)
Y2R
— Second Step Relay
Y2S
— Second Step Relay
OPTIONAL COMPONENTS LEGEND
[ ] DS
— Disconnect Switch
[ ] LWV — Leaving Water Valve
[ ] LP
— Loop Pump
Main Terminal Block
[ ] TB2 —
(460-v Units Only)
Terminal Block Disconnect
[ ] TB3 —
Switch (460-v Units only)
[ ] VES — Valve End Switch
Fig. 23 — Constant Torque Motor, Three-Phase/Single-Stage, Two-Step, E-Heat, Deluxe D Control
NOTES:
1. See unit name plate for electrical rating.
2. All field wiring must be in accordance with NEC-NFPA #70, copper conductors only - Conducteurs
en cuivre seulement.
3. 208/230-v units are factory wired for 230-v operation. For 208-v operation. Remove lead from 240
terminal and connect it to 208. Cap all unused terminals.
4. For alternate EMS coil voltages consult factory.
5. UPM-I includes built in:
270-300 second random start
300 second delay on break
120 second low pressure bypass.
6. "TEST" dip switch reduces delays to 10 sec when set to yes. must be set to "no" for normal opera-
tion.
7. "FREEZE SENSOR" on condenser will operate at 26°F by default; if 15°F operation is required,
Jumper R30 must be cut. If FREEZE SENSOR is not installed, a jumper shall be installed between
the FREEZE1 or FREEZE2 sensor terminals.
8. "ALARM OUTPUT" dip switch must be set to "PULSE" if blinking T-STAT service light is desired.
9. Default settings for UPM board from factory shown. Also see installation manual.
10. Alarm output is normally open (no) dry contact. if 24 VAC is needed, connect R to ALR-COM termi-
nal; 24VAC will be sensed on the ALR-OUT when the unit is in alarm condition. Output will be
pulsed if pulse is selected.
11. Terminal block TB3 located in side disconnect switch box.
12. Factory mounted loop pump or two way water valve. Both devices will not be present in the same
unit.
13. Refer to unit IOM for factory default motor speed instillation settings and available programmed
speed pins.
14. Loop pump are wired between line and neutral for 380-460-v units. For 208/230VAC units loop
pump is wired between lines.
15. When a loop pump is ordered, the aux relay contacts are used to power the pump.