Carrier Aquazone 50PTH024 Installation, Start-Up And Service Instructions Manual page 42

Two-stage water source heat pumps with puron refrigerant
Table of Contents

Advertisement

Table 14 — 50PT 024 Typical Unit Operating Pressures and Temperatures (Part Load)
ENTERING
WATER
MODEL
WATER
FLOW
TEMP (°F)
(GPM/TON)
30
40
50
60
50PT 024
Part Load
70
80
90
100
NOTE(S):
a. These operating temperatures and pressure charts show approximate temperatures and pressures for a unit on good repair. The values shown are
meant as a guide only and should not be used to estimate system charge.
b. This chart assumes rated air flow and 80°F db/67°F wb entering air temperature in cooling, 70°F db entering air temperature in heating.
c. Heating data at entering fluid temperatures below 50°F assumes the use of antifreeze. As a result of continuing research and development, speci-
fication are subject to change without notice.
LEGEND
DB — Dry Bulb
WB — Wet Bulb
— No operation in this temperature range.
Table 15 — 50PT 024 Typical Unit Operating Pressures and Temperatures (Full Load)
ENTERING
WATER
MODEL
WATER
TEMP (°F)
(GPM/TON)
30
40
50
60
50PT 024
Full Load
70
80
90
100
NOTE(S):
a. These operating temperatures and pressure charts show approximate temperatures and pressures for a unit on good repair. The values shown are
meant as a guide only and should not be used to estimate system charge.
b. This chart assumes rated air flow and 80°F db/67°F wb entering air temperature in cooling, 70°F db entering air temperature in heating.
c. Heating data at entering fluid temperatures below 50°F assumes the use of antifreeze. As a result of continuing research and development, speci-
fication are subject to change without notice.
LEGEND
DB — Dry Bulb
WB — Wet Bulb
— No operation in this temperature range.
COOLING
Suction
Discharge
Pressure
Pressure
(PSIG)
(PSIG)
1.4
1.9
1.4
106-129
146-178
1.9
102-124
133-162
1.4
115-141
180-220
1.9
111-135
163-200
1.4
124-152
213-261
1.9
120-146
194-237
1.4
134-163
247-302
1.9
128-187
225-275
1.4
143-175
281-343
1.9
137-168
255-312
1.4
152-186
315-385
1.9
146-179
286-350
1.4
161-197
349-426
1.9
155-190
317-387
Suction
Discharge
FLOW
Pressure
Pressure
(PSIG)
(PSIG)
1.8
2.4
1.8
112-137
144-176
2.4
106-130
137-167
1.8
116-142
177-217
2.4
111-135
169-206
1.8
121-148
211-258
2.4
115-140
200-245
1.8
126-154
245-299
2.4
119-146
232-284
1.8
130-159
278-340
2.4
124-151
264-323
1.8
135-165
312-381
2.4
128-157
296-362
1.8
140-171
345-422
2.4
133-162
328-401
Water
Air Temp
Temp
Drop
Rise (°F)
(°F) DB
17-21
18-22
10-13
19-23
17-20
17-21
10-12
18-23
16-19
17-21
10-12
18-22
15-19
17-20
9-11
18-21
14-18
16-20
9-11
17-21
14-17
16-19
8-10
17-20
13-16
15-19
8-10
16-20
COOLING
Water
Air Temp
Temp
Drop
Rise (°F)
(°F) DB
14-17
22-27
10-12
23-28
13-16
21-26
9-12
22-27
13-16
21-26
9-11
22-27
13-15
20-25
9-11
21-26
12-15
20-24
9-11
21-26
12-15
19-24
9-10
20-25
12-14
19-23
8-10
20-24
42
HEATING
Suction
Discharge
Pressure
Pressure
(PSIG)
(PSIG)
Rise (°F)
58-68
275-285
62-72
280-290
71-81
290-300
77-87
296-306
88-98
308-318
95-105
315-325
105-115
324-334
114-124
331-341
125-135
340-350
135-145
348-358
146-156
356-366
159-169
366-376
169-179
374-384
186-196
386-396
HEATING
Suction
Discharge
Pressure
Pressure
(PSIG)
(PSIG)
91-111
251-307
95-116
256-313
107-130
267-327
112-137
273-333
123-150
284-347
129-158
289-353
139-170
300-366
146-179
306-374
156-190
316-386
163-200
322-394
172-210
332-406
180-220
339-414
188-230
349-426
197-241
355-434
a,b,c
Water
Air Temp.
Temp.
Drop (°F)
5-6
19-23
3-4
20-24
7-8
22-26
4-5
23-27
7-8
25-29
4-5
27-31
9-10
28-32
5-6
30-34
10-11
32-36
6-7
33-37
12-13
35-39
7-8
37-41
13-14
39-43
8-9
41-45
a,b,c
Water
Air Temp.
Temp.
Drop (°F)
Rise (°F)
5-6
21-25
3-4
22-26
6-7
24-29
4-5
25-30
7-9
27-33
5-6
28-34
8-10
30-37
6-7
32-39
9-12
33-41
7-8
35-43
11-13
36-44
8-9
38-47
12-15
39-48
8-10
41-51

Hide quick links: