Filter Arrangment - Bryant 935SB Installation, Operating And Maintenance Instruction

Single-stage, upflow/horizontal ultra low nox, 35-in. tall, condensing gas furnace
Table of Contents

Advertisement

935SB: Installation, Start-up, Operating and Service Maintenance Instructions
Fig. 32 – Working Platform for Attic Installation
NOTE: Furnace shown is a direct vent application. Refer to the venting
section for allowable vent configurations.
NOTE: N Coil only, add 8-in. separation between coil and furnace for
all other unshielded coils. (See evaporator coil spacer or shield
requirements.)
NOTE: Local codes may require a drain pan and condensate trap when a
condensing furnace is installed over a finished ceiling.
Fig. 33 – Suspended Furnace Installation
NOTE: Furnace shown is a direct vent application. Refer to the venting
section for allowable vent configurations.
NOTE: N Coil only, add 8-in. separation between coil and furnace for
all other unshielded coils. (See evaporator coil spacer or shield
requirements.)
NOTE: Local codes may require a drain pan and condensate trap when a
condensing furnace is installed over a finished ceiling.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size that
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
the heat exchanger can be viewed for possible openings using light
assistance or a probe can be inserted for sampling the air stream. The
cover attachment shall prevent leaks.
Connect supply-air duct to flanges on furnace supply-air outlet. Bend
flange upward to 90° with wide duct pliers (see
duct must be connected to ONLY the furnace supply-outlet-air duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace casing side to attach supply air duct, humidifier, or other
accessories. All supply-side accessories MUST be connected to duct
external to furnace main casing.
Return Air Connections
The return-air duct may be connected to bottom of the furnace. The side
of casing that faces downward may also be used for return air
connection. A combination of the bottom and downward facing side may
also be used. The upward facing side of the casing cannot be used as a
return air connection (see
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel (see
Side Return Air Inlet
A200088
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when side return air
inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections
(see
Fig.
29). Where required by code, seal bottom closure to furnace
with tape, mastic, or other durable sealing method.
1. Lay furnace on the back or side
2. Remove the two (2) screws that secure the bottom closure panel to
the furnace casing and remove the panel
Fig. 34 – Removing Bottom Closure Panel (2 Screws)

FILTER ARRANGMENT

A200085
FIRE, CARBON MONOXIDE AND POISONING
HAZARD
Failure to follow this warning could result in fire, personal injury or
death.
Never operate a furnace without a filter or filtration device installed.
Never operate a furnace with filter or filtration device access doors
removed.
20
Fig.
27). The supply-air
Fig.
29).
Fig.
34).
WARNING
!
A170123

Advertisement

Table of Contents
loading

Table of Contents