Greenheck DOAS v8.1 Reference Manual page 48

Microprocessor controller
Table of Contents

Advertisement

Unit Status Mode Table (AV-40)
0
Off/Standby
1
Unoccupied Start
2
Occupied Start
3
Opening Dampers
5
Dampers Open
6
Fan Start Delay
7
Exhaust Fan Start
8
Supply Fan Start
9
Startup Delay
10
System On
11
Soft Shutdown
12
System Disabled
13
Remote Off
14
System Shutdown Alarm
15
Pressurization Only
16
Exhaust Only
17
Fans Only Purge
18
Case Heat Active
19
Fans Only
20
Economizing
21
Cooling
22
Heating
23
Dehumidifying
25
HGRH Purging
26
Energy Recovery Defrost Active
29
Dehumidifying w/Heat
30
Overrides
31
Expansion Offline
33
Energy Recovery Active
34
Hot Gas Reheat Active
35
Morning Warm Up/Cool Down Active (Sequence)
36
Heat Pump Defrost
48
Microprocessor Controller for DOAS
Appendix E: Points List
Alarm Table - Latest Alarm (BACnet IV-5 or Modbus 30202)
0
No Active Alarms
1
Supply Fan 1 Run - Status Not Proven
2
Freeze Protection - Thermostat Tripped
3
High Supply Duct - Static Pressure
4
Low Return Duct - Static Pressure
5
Outside Air Temp - Sensor Value Not Valid
6
Supply Air Temperature - Sensor Value Not Valid
7
Cold Coil 1 Temp - Sensor Value Not Valid
9
Exhaust Air Temp - Sensor Value Not Valid
10
Mixed Air Temperature - Sensor Value Not Valid
11
Return Air Temperature - Sensor Value Not Valid
12
Space Temperature - Sensor Value Not Valid
13
Return Air RH - Sensor Value Not Valid
14
Space RH - Sensor Value Not Valid
15
Outside RH - Sensor Value Not Valid
16
Low Pressure Switch - Circuit A
17
Low Pressure Switch - Circuit B
20
High Pressure Switch - Circuit A
21
High Pressure Switch - Circuit B
24
Damper End Switch Fail - Dampers are not open
25
Exhaust Fan 1 Run - Status Not Proven
26
Filters are Dirty - Replace Filters
27
Cond Drain Pan Full - Check Drain
28
Exp Board 1 Status - Board is Offline
29
Exp Board 2 Status - Board is Offline
31
Exp Board 4 Status - Board is Offline
32
Non-Volatile Memory Er - Contact Tech Support
33
Space 1 CO2 - Sensor Value Not Valid
34
Space Static Pressure - Sensor Value Not Valid
35
Supply Duct Stat Press - Sensor Value Not Valid
36
Return Duct Stat Press - Sensor Value Not Valid
37
Sup Fan AFMS - Sensor Value Not Valid
38
Exh Fan AFMS - Sensor Value Not Valid
39
Outside Damper AFMS - Sensor Value Not Valid
40
Space Setpt Adj Slider - Sensor Value Not Valid
41
Space 2 CO2 - Sensor Value Not Valid
42
Return CO2 - Sensor Value Not Valid
43
Discharge Press Ckt A - Sensor Value Not Valid
44
Discharge Press Ckt B - Sensor Value Not Valid
47
Suction Press Ckt A - Sensor Value Not Valid
48
Suction Press Ckt B - Sensor Value Not Valid
51
Discharge Temp Ckt A - Sensor Value Not Valid
52
Discharge Temp Ckt B - Sensor Value Not Valid
55
Suction Temp Ckt A - Sensor Value Not Valid