Siemens SITRANS LG240 Operating Instructions Manual page 29

Guided wave radar profibus pa polished rod probe
Hide thumbs Also See for SITRANS LG240:
Table of Contents

Advertisement

Application - Medium
type
Application - Application
Application - Medium,
dielectric constant
Application - Gas phase
PBD-51041044
In this menu item you can select which type of medium you want to
measure. You can choose between liquid or bulk solid.
In this menu item, you can select the application. You can choose
between level measurement and interface measurement. You can
also choose between measurement in a vessel or in a bypass or
standpipe.
Note:
The selection of the application has a considerable influence on all
other menu items. Keep in mind that as you continue with the param-
eter adjustment, individual menu items are only optionally available.
You have the option of choosing the demonstration mode. This mode
is only suitable for test and demonstration purposes. In this mode, the
sensor ignores the parameters of the application and reacts immedi-
ately to any change.
In this menu item, you can define the type of medium (product).
This menu item is only available if you have selected level measure-
ment under the menu item "Application".
You can choose between the following medium types:
Dielectric con-
Type of medium
stant
> 10
Water-based liq-
uids
3 ... 10
Chemical mix-
tures
< 3
Hydrocarbons
This menu item is only available, if you have chosen interface meas-
urement under the menu item "Application". In this menu item you can
enter if there is a superimposed gas phase in your application.
Only set the function to "Yes", if the gas phase is permanently pre-
sent.
SITRANS LG240 - Operating Instructions
Examples
Acids, alcalis, water
Chlorobenzene, nitro lacquer, aniline,
isocyanate, chloroform
Solvents, oils, liquid gas
29