Trane 4YCZ6024A1060A Installation And Operation Manual page 22

Single packaged gas/electric 16 seer convertible, 2 - 5 ton, 60 - 115 kbtu, r-410a
Table of Contents

Advertisement

U U n n i i t t I I n n s s t t a a l l l l a a t t i i o o n n
1 Cu. Ft. Dial Gas Flow CFH = Chart Flow
Reading / 2
1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow
Reading / 4
5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow
Reading / 4
N N o o t t e e : : For manifold pressures and orifice sizes for
gas with other BTU ratings, contact the local
gas utility. Manifold pressure should be 3.5
inches water column (+ 0.1). Input for natural
gas must n n o o t t exceed the value shown on the
rating plate.
6. Multiply the final figure by the heating value of the
gas obtained from the utility company and compare
Outlet Pressure Boss
Inlet Pres
sure Boss
Gas Valve
ON/OFF
High Fire Coil
Toggle
Terminal (H)
Switch
Table 11. Gas Flow (in cfh)
Sec.
Flow
Sec.
Flow
8
900
29
248
9
800
30
240
10
720
31
232
11
655
32
225
12
600
33
218
13
555
34
212
14
514
35
206
15
480
36
200
16
450
37
195
17
424
38
189
18
400
39
185
19
379
40
180
20
360
41
176
21
343
42
172
22
Figure 6. Burner and Valve
2nd Stage (HI)
Manifold Pressure
Adjustment
Regulator
Vent
1st Stage (LO)
Manifold
Pressure
Adjustment
Coaxial Coil
Terminal (M)
Common
Terminal (C)
Sec.
Flow
Sec.
Flow
50
144
82
88
51
141
84
86
52
138
86
84
53
136
88
82
54
133
90
80
55
131
92
78
56
129
94
76
57
126
96
75
58
124
98
73
59
122
100
72
60
120
104
69
62
116
108
67
64
112
112
64
66
109
116
62
to the nameplate rating. This must not exceed the
nameplate rating.
7. Changes can be made by adjusting the manifold
pressure.
a. Attach a manifold pressure gauge to the Outlet
Pressure Tap.
b. Remove the cover screw on top of the gas valve
to access the manifold pressure adjustment
screw.
c. Turn the adjustment screw in to increase the
gas flow rate, and out to decrease the gas flow
rate using a 3/32" hex wrench or flat-head
screwdriver.
Table 11. Gas Flow (in cfh) (continued)
Sec.
Flow
Sec.
Flow
22
327
43
167
23
313
44
164
24
300
45
160
25
288
46
157
26
277
47
153
27
267
48
150
28
257
49
147
H H i i g g h h A A l l t t i i t t u u d d e e I I n n s s t t a a l l l l a a t t i i o o n n
Unit nameplate ratings are based on equipment
operation from sea level to 2000 feet elevation above
sea level. No orifice changes required for high altitude
installation, please refer to below chart for rating
information.
Sec.
Flow
Sec.
Flow
68
106
120
60
70
103
124
58
72
100
128
56
74
97
132
54
76
95
136
53
78
92
140
51
80
90
144
50
18-EB28D1-12C-EN