UTICA BOILERS SFH 5 Series Installation, Operation & Maintenance Manual page 25

Water oil fired cast iron boiler
Table of Contents

Advertisement

B. Ignition failure - with burner off, close oil supply
valve and run through start-up procedure, The safety
switch should lock out as in flame failure.
C. Power failure - Turn off main power supply switch
while burner is operating� When burner stops, restore
power and burner should start�
If operation is not as described as above, check
wiring and controls�
14.6 Preventive Maintenance
Inspect boiler and vent pipe for accumulation of soot or
scale deposits periodically, at least once every year before
start of each heating season� When soot is present on
section walls and flueways, improper combustion will result,
causing additional sooting and scaling until flueways are
completely closed. To remove soot and scale from flueways,
remove top jacket panel, top clean-out plate, open burner
swing door� See Figure #22�
Periodic inspection and tightening of tankless heater/cover
plate bolts will reduce risk of leaks�
14.7 Instructions For Opening Burner Swing
Door
1.
Turn off power to boiler.
2.
Allow boiler to cool down�
3.
Disconnect power cable at burner electrical quick
connect� See Figure #22.
4.
Loosen screws on the sides of lower front jacket panel�
5.
Pull bottom part of lower front panel forward�
6.
Lift lower front panel up and off boiler.
7.
Close oil shutoff valve. See Figures #17 & #18�
8.
Disconnect oil line from burner�
9.
Do not try to swing door with oil line attached�
10.
Remove nut from swing door stud on right hand side of
door�
11.
Swing open burner and door to the left�
14.8 Instructions For Closing Burner Swing Door
1.
Swing burner and door to right until insulation is
slightly compressed and stud is exposed�
2.
Attach nut to stud and tighten until built in stop
contacts the mounting door�
3.
Replace oil line to burner�
4.
Replace lower jacket panel, and tighten screws�
5.
Connect power cable at burner electrical quick connect�
6.
Turn on power to boiler. Open oil shutoff valve.
7.
Bleed oil line�
14 - OPERATING INSTRUCTIONS
-
25
14.9 Start of Heating System
• Using flue brush, brush soot and scale into combustion
space where it can be removed through swing door
opening�
• It is recommended to replace nozzle at start of each
heating season�
• Lubricate burner motor and circulator motor - if
required - with few drops of good grade light motor oil�
Do not over oil�
• Have service agent service burner, check controls and
check electrodes for carbon or cracks in insulators�
• Set burners to produce conditions shown in Start-up
and Adjustment of Oil Burner procedure as stated in
this section�
• Use caution when vacuuming in chamber area� Damage
to chamber could result�
Figure #22
PN 240013073, Rev. A [08/31/2020]

Advertisement

Table of Contents
loading

Table of Contents