Step 6: Wiring Boiler - HydroTherm VGAB Series Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Testing Gas Piping
For any pressure testing in excess of 1/2 psi, the boiler
and its individual shutoff valve must be isolated from the
piping system by disconnecting
them and capping the
outlet(s). For any pressure testing equal to or less than
1/2 psi, the boiler must be isolated
from the piping
system by closing its manual shutoff valve.
Minimum pressure required at the gas valve inlet is 5"
W.C. for natural
gas and
11" W.C. for propane.
Maximum pressure allowable at the gas valve inlet is 12"
W.C. If the gas pressure
is above
these
limits,
a
pressure regulator must be installed. If the gas pressure
is below these limits, contact the local utility.
STEP 6: WIRING
THE BOILER
All electrical and control wiring must be installed in ac-
cordance
with the codes
listed in Section
1 of this
manual. Follow the wiring diagram for your particular
installation as shown in Figures 2.13 through 2.20.
For United States only, VGA-350B and 400B natural gas
standing pilot units have a secondary
pressuretrol
(lo-
cated to the right of the primary pressuretrol
when fac-
ing the front of the boiler). Connect wiring assemblies
(provided on boiler) from the low water cut-off or trans-
former to the primary pressure control and from the gas
valve to the secondary pressure control as shown in Fig.
2.9. Do not readjust
the secondary
pressuretrol;
its
purpose is to interrupt thermocouple
power to the gas
valve in case the primary pressuretrol fails to function.
M&M #67
LWCO
FOR FIELD
CONNECTION
TO PRIMARY
PRESSURE
CONTROL
(ON THE LEFT)
TRANSFORMER
!_:_=i
o o i:
GAS
VALVE
FOR FIELD
CONNECTION
TO SECONDARY
PRESSURE
CONTROL
(ON THE RIGHT)
WIRE
ASS'Y.
400 SERIES
ORM&M
PS804 LWCO
FOR BOILERS EQUIPPED WITH
MCDONNELL-MILLER
LWCO
FOR BOILERS EQUIPPED WITH
MCDONNELL-MILLER
LWCO
FIGURE 2.12
FOR FIELD
FOR FIELD
CONNECTION
CONNECTION
TO PRIMARY
TO SECONDARY
PRESSURE
PRESSURE
CONTROL
CONTROL
(ON THE LEFT)
(ON THE RIGHT)
WIRE
ASS'Y.
I
FOR BOILERS EQUIPPED WITH
400 SERIES OR M&M PS804
FOR BOILERS EQUIPPED
400 SERIES OR M & M PS804 LWCO
11