¢ Dip switch setting
Remote controller address setting:
When operating a number of indoor units by using a wired remote controller, DIP switch setting
for assigning unit number to each indoor unit is required.
DIP switches are normally set to make the unit number 00.
Remote
controller
address
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
¢ Jumper wire setting
• Drainage function setting (JM1)
Connect
Disconnect
• Auto louver grille setting (JM2)
When auto louver grille kit (optional parts) is attached, set the auto louver grille setting "En-
able".
Connect
Disconnect
• Fan delay setting (JM3)
Connect
Disconnect
8-1. Indoor unit (setting by DIP switch and jumper wire)
DIP switch number
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
JM1
JM2
JM3
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Function
Enable
Disable
Function
Disable
Enable
Function
Disable
Enable
- 262 -
Factory setting
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
Factory setting
Factory setting