¢ External output
With using external output function, some status signals are transmitted to the control PCB, and the
related LED lamp indicates the status of this product.
Error status output
Signal on air conditioner error status is generated when a malfunction occurs.
• Circuit diagram example (CN136)
Outdoor unit
control PCB
Connector
+
1
CN136
2
Error status
Output signal
• Optional part
Part name
External connect kit
6-2. Outdoor unit
Connected unit
Vcc
Vcc
Power
supply
+
Load
-
*10 m
Signal
Locally purchased
Error
Normal
On
Off
Model name
UTY-XWZXZ3
• 1: Power supply
Voltage (Vcc): DC 24 V or less
• 2: Load
DC 500 mA or less
• *: Make the distance from the PCB to the con-
nected unit within 10 m.
- 234 -
Exterior