Connecting Up; Safety When Connecting Up - Siemens SIMATIC NET SCALANCE XCH-100 Equipment Manual

Table of Contents

Advertisement

Connecting up

5.1

Safety when connecting up

Safety notices
When connecting up the device, keep to the safety notices listed below.
Operate the device with a power supply according to "Limited Energy". When connecting up the
device, keep to the safety notices listed below.
Safety notices for operation with a power supply according to "Limited Energy"
1. If the device is supplied by a power supply with limited power (Limited Energy) that
2. If the device is operated with a power supply for without power limitation and the entire
3. If the device is operated with a power supply without power limitation and the entire power
SCALANCE XCH-100/XCM-100
Equipment Manual, 11/2022, C79000-G8976-C662-01
WARNING
complies with IEC/UL61010-1 or VDE 0805-1, no additional power limitation is required
according to National Electrical Code (r) (ANSI/NFPA 70).
If the device is connected to a redundant power supply (two separate power supplies), the
combination of the two power supplies must meet these requirements.
To comply with EU Directive 2014/34/EU (ATEX 114), UK Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at
least IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7,
GB 3836.3.
power requirement does not exceed 100 W, a fuse must be installed between the power
supply and each supply input of the device to meet the requirements for limited power
(Limited Energy) according to IEC/UL61010-1 or VDE 0805-1. For more information, see
"Suitable fusing for the power supply cables" below.
To comply with EU Directive 2014/34/EU (ATEX 114), UK Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at
least IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7,
GB 3836.3.
requirement exceeds 100 W, the device must be installed in a fire protection housing
according to ANSI/UL-61010-1:2018, paragraph 9.3.
5
33