Figure 12 - Variable Speed Drive Bracket; Table 9 - Vsd Weight - York YD Manual

Centrifugal liquid chillers
Hide thumbs Also See for YD:
Table of Contents

Advertisement

FORM 160.69-NM4
ISSUE DATE: 9/30/2020
VSD Re-assembly
1. Install VSD bracket assembly.
2. Lift the Variable Speed Drive and remove all
packing material, for Variable Speed Drive
weight refer to Table 9 on page 21. Care-
fully lower the Variable Speed Drive on to the
supports on the condenser. Fasten the Variable
Speed Drive to the condenser and to the motor
terminal box duct. Make all necessary connec-
tions for the VSD cooling loop to be complete.
The Variable Speed Drive will be shipped with
glycol in the cooling system. The Variable Speed
Drive coolant must be changed to the inhibitor
provided with the shipped loose items prior to
starting the unit.
Note: Approximate 1,000 lbs.

FIGURE 12 - VARIABLE SPEED DRIVE BRACKET

TABLE 9 - VSD WEIGHT

MOTOR
HP RANGE
CODE
CW - DA
655 - 1000
CV - CZ
608 - 790
CA - DB
845 - 1100
5CT - 5DA
704 - 1000
JOHNSON CONTROLS
LD19865
VSD WEIGHT TABLE
VSD (UNIT MOUNTED LV VSD)
VSD
RATED
JOB MAX HP
VOLTAGE
845
380
790
460
1048
460
917
380/400
FIGURE 13 - VSD BRACKET INSTALLED
HZ
W/OUT FILTER
60
1700 (771)
60
1500 (680)
60
1700 (771)
50
1720 (780)
LD19850
LD19852
VSD WEIGHT
WITH FILTER
2060 (934)
1840 (835)
2060 (934)
2080 (943)
21