CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:
(AB + AC + BC)/3 = AVERAGE VOLTAGE =_____________ V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = _______________V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =______________
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START-UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
COMPRESSOR AMPS (L1/L2/L3)
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES: ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT 1/8 to 1/3 FULL? (Y/N)_______________
NOTES:
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
© 2022 Carrier
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
AB_____________ V
Edition Date: 1-22
Printed in U.S.A.
AC______________ V
COMP A1
______________
______________
______________
______________
______________
______________
______________
______________
______________
______________
______________
____/____/____
BC_____________ V
COMP B1
____________
____________
____________
____________
____________
____________
____________
____________
____________
____________
____________
____/____/____
Form No: II524J-7-16-02 Rev. A
CL-2
Replaces: II524J-7-16-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

524j 08524j 12524j 14524j 16

Table of Contents