10.3 Adding Refrigerant
In North America, the standard pipe length is 7.5m (25'). The minimum length is
10ft. The factory charge is suitable for pipe lengths of 10 -25ft. If piping length
exceeds 25ft, the additional refrigerant to be charged can be calculated using the
formula in Table 9. For multi-zone units refer to the multi-zone installation and
operation manual.
Additional refrigerant per pipe length
Connective Pipe
< Standard pipe length
> Standard pipe length
Table 9
Single zone refrigerant pipe summary
Model - Single Zone
IDU
BMS500-AAS009-1CSXRC
BMS500-AAU009-1AHCXB
BMS500-AAS009-1CSXHC
BMS500-AAS012-1CSXRC
BMS500-AAU012-1AHCXB
BMS500-AAS012-1CSXHC
BMS500-AAS018-1CSXRC
BMS500-AAU018-1AHCXB
BMS500-AAS018-1CSXHC
BMS500-AAS024-1CSXRC
BMS500-AAU024-1AHCXC
BMS500-AAS024-1CSXRC
BMS500-AAU036-1AHCXC
BMS500-AAS036-1CSXLC
BMS500-AAU048-1AHCXC
BMS500-AAS048-1CSXLC
Table 10
CAUTION: CONTAINS REFRIGERANT
NEVER mix refrigerant types.
Bosch Climate 5000 Series Four Way Cassette Ductless Split Air Conditioner / Heat Pump (06.2022)
Liquid Side: Ø 6.35 (ø 1/4")
Inverter R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oz/ft
Capacity (Btu/h)
ODU
9K
12K
18K
24K
36K
48K
Additional Refrigerant
N/A
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oz/ft
IDU
Max. Equivalent Length
Liquid Line
Vapor Line
1/4"
3/8"
1/4"
1/2"
1/4"
1/2"
1/4"
1/2"
3/8"
5/8"
3/8"
5/8"
Installation Instructions
Liquid Side: Ø 9.52 (ø 3/8")
Inverter R410A:
Max. Height Variation
m(ft)
m(ft)
30 (98ft)
20 (66ft)
30 (98ft)
20 (66ft)
30 (98ft)
20 (66ft)
50 (164ft)
25 (82ft)
65 (213ft)
30 (98ft)
65 (213ft)
30 (98ft)
| 27