Heavy-Duty Version - Samson 4747 Mounting And Operating Instructions

Limit switch
Table of Contents

Advertisement

5.6.2

Heavy-duty version

Î See Fig. 7.
Î Required mounting parts and accesso-
ries: section 3.3 on page 15.
1. Prepare actuator and mount possibly re-
quired adapter supplied by the actuator
manufacturer (only necessary for fixing
level 2).
2. Mount the housing (7) onto the rotary
actuator. In case of VDI/VDE attachment,
place spacers (8) underneath, if neces-
sary.
3. For SAMSON Type 3278, VETEC S160
and VETEC R Rotary Actuators, screw
the adapter (6) with the supplementary
adapter (depending on the mounting kit)
onto the free end of the shaft of the actu-
ator. For VDI/VDE version, only place on
the adapter (6) when it is required for
the actuator size.
4. Stick adhesive label onto the coupling
wheel (5) in such a manner that the yel-
low part of the sticker is visible in the
window of the housing when the valve is
OPEN. Adhesive labels with explanatory
symbols are enclosed and can be stuck
on the housing, if required.
5. Fasten coupling wheel (5) on the slotted
actuator shaft or adapter (6) using screw
(3) and disk spring (4).
6. Unscrew the standard follower pin from
the limit switch's M lever (1). Attach the
follower pin (Ø5 mm) included in the
mounting kit to pin position 90°.
EB 4747 EN
7. Fasten the limit switch onto the mounting
plate (2).
8. Place the limit switch together with the
mounting plate on the enclosure (7) and
screw it tight. Taking the actuator's direc-
tion of rotation into account, adjust lever
(1) so that it engages in the correct slot
with its follower pin.
Mounting
31

Advertisement

Table of Contents
loading