Quick Reference Guide - Generac Power Systems 10 kW Owner's Manual

60 hz air-cooled generator
Hide thumbs Also See for 10 kW:
Table of Contents

Advertisement

Quick Reference Guide

To clear an active alarm, press OFF button on the control panel, then the ENTER button, and
finally the AUTO button. Contact an IASD if alarm reoccurs.
Active Alarm
LED
FLASH-
NONE
GREEN
HIGH
TEMPERA-
RED
TURE
OVERLOAD
REMOVE
RED
LOAD
RPM SENSE
RED
LOSS
NOT
NONE
ACTIVATED
NONE
GREEN
LOW OIL
RED
PRESSURE
RPM SENSE
RED
LOSS
OVERCRANK
RED
LOW VOLTS
RED
REMOVE
LOAD
OVERSPEED
RED
UNDER-
RED
VOLTAGE
UNDER-
RED
SPEED
Owner's Manual for 60 Hz Air-Cooled Generators
Problem
Unit running in
ING
AUTO but no
power in house.
Unit shuts down
during operation.
Unit shuts down
during operation.
Unit was running
and shut down,
attempts to
restart.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Unit will not start
in AUTO with util-
ity loss.
Troubleshooting / Quick Reference Guide
Action
Check genera-
Check generator MLCB (gen-
tor MLCB (gen-
erator disconnect). If it is ON,
erator
contact an IASD.
disconnect).
Inspect ventilation around gen-
Check LEDs /
erator, intake, exhaust, and
screen for
rear of generator. If no obstruc-
alarms.
tions are present, contact an
IASD.
Check LEDs /
Clear
screen for
household loads from genera-
alarms.
tor. Put in AUTO and restart.
Clear
Check LEDs /
household loads from genera-
screen for
tor. Put into AUTO and restart.
alarms.
If generator does not start, con-
tact an IASD.
Check if screen
See Activation section in instal-
says unit not
lation manual.
activated.
Check screen
If startup delay is greater than
for start delay
expected, contact an IASD to
countdown.
adjust from 2 to 1500 seconds.
Check LEDs /
Check oil level and add oil as
screen for
needed. If oil level is correct,
alarms.
contact an IASD.
Clear alarm. Using control
panel, check battery by navi-
gating to BATTERY MENU
Check LEDs /
option from MAIN MENU. If
screen for
battery
alarms.
GOOD, contact an IASD. If
control panel displays CHECK
BATTERY, replace battery.
Verify fuel line shutoff valve is
Check LEDs /
ON. Clear alarm. Start unit in
screen for
MANUAL. If it does not start, or
alarms.
starts and runs rough, contact
an IASD.
Check LEDs /
Clear
screen for
household loads from genera-
alarms.
tor. Put in AUTO and restart.
Check LEDs /
screen for
Contact an IASD.
alarms.
Check LEDs /
screen for
Contact an IASD.
alarms.
Check LEDs /
screen for
Contact an IASD.
alarms.
Solution
alarm
and
remove
alarm
and
remove
condition
displays
alarm
and
remove
34