Maintenance
1.
Inspect engine tag for oil viscosity and
classification. Drain and fill with recom-
mended oil if necessary.
2.
Verify state of battery. Fill all cells of
unsealed batteries to correct level with dis-
tilled water. DO NOT use tap water.
Charge battery to 100% state of charge.
Replace battery if faulty.
3.
Clean and wipe down generator enclo-
sure.
4.
Verify 7.5A fuse is removed from genera-
tor control panel.
5.
Connect battery. Observe battery polarity.
Damage will occur if battery is connected
incorrectly. Install positive battery cable
first.
6.
Connect battery charger AC input T1/Neu-
tral cable (with white sleeve) at controller.
7.
Open fuel shutoff valve.
8.
Insert 7.5 A fuse into generator control
panel.
9.
Complete Install Wizard procedure (dia-
grammed in generator installation man-
ual).
10.
Press MANUAL button to start unit. Allow
unit to warm up for a few minutes.
11.
Press OFF button to stop unit.
12.
Set generator MLCB (generator discon-
nect) to ON (CLOSED).
13.
Press AUTO button on control panel.
The generator is ready for service.
NOTE: Exercise timer and current date and
time must be reset if battery is discharged or
has been disconnected.