Section 5: Troubleshooting / Quick Reference Guide

Generator Troubleshooting

Problem
Cause
Blown fuse.
Loose, corroded, or faulty battery
cables.
Engine will not
crank
Faulty starter contact.
Faulty starter motor.
Discharged battery.
No fuel.
Faulty fuel solenoid (FS).
Harness/wiring issue.
Engine cranks
but will not start
Faulty spark plug(s).
Valve clearance out of adjust-
ment, if applicable. See Engine.
Plugged or damaged air cleaner.
Faulty spark plug(s).
Incorrect fuel pressure.
Engine starts
hard and runs
rough
Fuel selector in wrong position.
Valve clearance out of adjust-
ment, if applicable. See Engine.
Internal engine issue.
Unit is set to
Controller wired incorrectly.
OFF, but
engine contin-
Faulty control board.
ues to run
Generator MLCB (generator dis-
connect) is OFF (OPEN).
No AC output
Generator internal failure.
from generator
Engine may be warming up. See
Cold Smart
Owner's Manual for 60 Hz Air-Cooled Generators
Start.
Troubleshooting / Quick Reference Guide
Correction
Correct short circuit condition by replacing
7.5 A fuse in generator control panel. Con-
tact an IASD if fuse continues to blow.
Tighten, clean, or replace as necessary.*
Charge or replace battery.
Replenish fuel / turn on fuel valve.
Contact an IASD for assistance.
Inspect spark plug gap; replace spark
plug(s) if out of tolerance.
Inspect and adjust valve clearance.
Inspect and clean air cleaner.
Inspect spark plug gap; replace spark
plug(s) if out of tolerance.
Verify fuel pressure to regulator is 10–12 in
water column (2.49–2.99 kPa) for LP gas,
and 3.5–7.0 in water column (0.87–1.74
kPa) for NG.
Set fuel conversion valve to correct position
and program controller for fuel type.
Inspect and adjust valve clearance.
Contact an IASD for assistance.
Contact an IASD for assistance.
Set generator MLCB (generator discon-
nect) to ON (CLOSED).
Contact an IASD for assistance.
Check the controller screen to verify status.