INSTALLATION INSTRUCTIONS
If the dispersion tube must be mounted below the humidifier or
if the steam hose needs to run up and over an obstruction, a drip
tee with drain trap, Part #5628RP, must be installed as shown in
Figure 4 .
NOTICE
CONTROL CONDENSATE FLOW AND COLLECTION.
Failure to follow steam hose recommendations in this
manual can result in reduced or erratic performance,
increased noise and condensate in the duct.
DISTANCE FROM HUMIDIFIER TO DISPERSION TUBE
The capacity of the humidifier is reduced by the length of
the steam hose or pipe due to condensation . The maximum
recommended length of steam hose is 6 feet . Use hard pipe
insulated with 1" thick insulation rated for 212°F or higher
for lengths greater than 6 feet . Table 4 provides humidifier
capacity with various lengths of steam hose and pipe . If 6-foot
steam hose does not reach from humidifier to dispersion tube,
splice in 1" copper pipe using 3/4" x 1" reducing couplings as
shown in Figure 6 .
FIGURE 6
3/4" x 1"
Reducing Coupling
1-1/2" Hose Clamp
Steam Hose
(CONTINUED)
Dispersion
Tube
Steam Hose
1-1/2" Hose Clamp
1" Copper Pipe
Humidifier
90-1705
FIGURE 4 – Dispersion Tube Mounted Below Humidifier
Drip tee installation for
90° long
piping over obstruction,
sweep or two
or if dispersion tube is
45° elbows
lower than humidifier.
Insulate hard pipe to
reduce steam loss
6" min
8" min
1" air gap
Open drain required,
see note 1.
90-1703
FIGURE 5
Hose Clamp
Steam Hose
1" I.D.
(Downward
Slope from
Humidifier
to Tee)
Steam
Humidifier
Obstruction
Drip tee
Part #5628RP
Drain trap
NOTES:
1. Refer to governing codes for
drain pipe size and materials.
2. Support steam hose so there
are no sags or low spots.
Hose Clamp
To Steam
Dispersion Tube
Steam Hose, 1" I.D.
(Downward Slope to Tee)
Tee
Assembly
#5628RP KIT
CONTENTS:
Steam
Hose Clamps (5)
Hose
Trap (1)
1" I.D.
Tee Assembly (1)
Hose
Clamp
Flared
End
Trap
Note: Prime with water
before using humidifier
Hose Clamp
Drain Hose
7/8" I.D.
90-1844