Trane EHUMD800ASM00BA Installation & Maintenance Instructions Manual page 8

Steam humidifier
Hide thumbs Also See for EHUMD800ASM00BA:
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION INSTRUCTIONS
Each humidifier requires its own steam hose and dispersion tube. Do not connect steam hoses from more than one humidifier
together. Back-pressure from one humidifier can lower the water level in the canister in the other humidifier and cause
operational problems.
Do not install the dispersion tube in a duct with greater than 2 in. wg static pressure. High duct pressure can cause back-
pressure in the canister which can result in unstable unit operation.
TABLE 3 – Absorption Distance (Minimum distance from dispersion tube downstream to any obstruction or bend in duct)
Humidifier
Airflow Velocity*
Output (gal/day)
300 fpm
600 fpm
Up to 16 .0
1200 fpm
1800 fpm
300 fpm
600 fpm
20 .5 – 25 .0
1200 fpm
1800 fpm
300 fpm
600 fpm
25 .0 – 35 .0
1200 fpm
1800 fpm
*Velocity in feet per minute = Duct airflow volume in cubic feet per minute / duct area in square feet .
Example: 1,200 cfm through 16" x 12" duct = 1,200/(12 x 16/144 sq . in ./sq ft .) = 1,200/1 .333 = 900 fpm
ELEVATION
The preferred location for the dispersion tube is higher than the
humidifier so that the steam hose has a constant downward slope of at
least 2" per foot from the dispersion tube to the humidifier . If hard pipe
is used, the slope can be 1/4" per foot . With the constant downward
slope, any condensation that forms in the steam hose will drain back
into the steam canister . See Figure 3 .
8
(CONTINUED)
CAUTION
70°F & 30% RH
70°F & 45% RH
Setpoint
Setpoint
13"
6"
3"
2"
15"
6"
5"
3"
24"
17"
12"
10"
Insulate pipe with 1" fiberglass
65°F & 45% RH
Setpoint
19"
23"
10"
12"
5"
6"
3"
4"
23"
28"
12"
13"
6"
7"
4"
5"
31"
36"
22"
26"
15"
18"
13"
15"
FIGURE 3 – Dispersion Tube Mounted Above Humidifier
Steam hose or pipe.
to reduce steam loss.
90° long sweep
or two 45° elbows
45°F & 45% RH
Setpoint
30"
18"
13"
10"
45"
26"
19"
16"
60"
48"
25"
20"
5" minimum
Duct
Dispersion
tube
* Pitch steam hose down
from dispersion tube to
humidifier:
2"/ft (15%) minimum
when using steam hose.
1/4"/ft when using
hard pipe.
90-1704

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehumd800bsmlcba

Table of Contents