7. Setting Up
Walk Test Procedure
• Turn the power to the unit ON. The lamp will immediately illuminate
as the unit goes through its "warm-up" period. After approximately
1 minute the lamp will extinguish. This indicates the unit is
wired correctly and the unit is in Test Mode.
• Try to remain outside the detection area during the warm-up period.
• The unit will now operate during daytime as well as at night, illuminating the
lamp for approx. 5 seconds each time. This allows testing to be carried out
to establish whether the sensor is covering the required area.
• Walk across the location the sensor is fitted, to establish the detection area.
• The sensor will detect you approximately up to 9 metres forward at mounting
height of 1m.
• As you cross a detection "zone" the lamp will illuminate. Now stand still
until the lamp extinguishes (this should take approx. 5 seconds).
• Start moving again after 2 seconds. As you cross each "zone" the lamp
will illuminate.
• Repeat the above, walking at various distances and angles to the unit.
This will help you to confirm the detection pattern.