Electronic Combustion Control Unit - Viessmann Vitodens 050-W Installation And Service Instructions Manual

Table of Contents

Advertisement

Specification
(cont.)
Flue system types
Available in the following countries
AE, AM, AT, AZ, BA, BG, BY, CH, CY, CZ, DK, EE, ES,
FI, FR, GB, GR, HR, HU, IE, IS, IT, KG, KZ, LT, LV, MD,
ME, MT, NL, NO, PL, PT, RO, RS, RU, SE, SK, TR, UA,
UZ
AU, BE, NZ
DE, LU, SI
CN
Gas categories
Available in the following countries
AE,AM, AT, DK, EE, KG, LV, LU, LT, RO, RU, SE AZ,
BA, BG, BY, CH, CZ, ES, FI, GB, GR, HR, IE, IS, KZ,
IT, MD, ME, NO, PT, RS, SI, SK, TR, UZ HU, MT, UA
AU, BE, NZ
DE, FR
CY
NL
PL
CN
The gas condensing boiler is suitable for operation
with a hydrogen blend of up to 20 % by volume.

Electronic combustion control unit

The electronic combustion controller utilises the physi-
cal correlation between the level of the ionisation cur-
rent and the air ratio
. The maximum ionisation cur-
λ
rent is achieved at an air ratio of 1 for all gas qualities.
The ionisation signal is evaluated by the combustion
controller. The air ratio is regulated to a value that is
between
= 1.2 and 1.5. This range provides for an
λ
optimum combustion quality. Thereafter, the electronic
gas train regulates the required gas volume subject to
the prevailing gas quality.
To check the combustion quality, the CO
the O
content of the flue gas is measured. The pre-
2
vailing air ratio is determined using the actual values.
Only for specifically marked appliances.
*4
96
Flue system types
B
, B
23
23P
(C
, C
43
43P
B
, B
23
23P
(C
, C
43
43P
B
, B
23
23P
(C
, C
43
43P
C13
Gas categories
II
/II
2N3P
2H3P
I
2N
II
2N3P
I
3P
II
2EK3P
II
/II
2N3P
2ELw3P
12T
To achieve optimum combustion control, the system
regularly carries out an automatic self-calibration; also
after power failures (shutdown). For this, the combus-
tion is briefly regulated to maximum ionisation current
(corresponding to air ratio
place shortly after the burner starts. The process lasts
approx. 20 s during which higher than normal CO
emissions may occur briefly.
content or
2
, B
, C
, C
, C
, C
, C
33
13
33
53
63
, C
)
*4
(10)3
, B
, C
, C
, C
, C
, C
33
13
33
53
83
, C
, C
)
*4
(10)3
(14)3
, B
, C
, C
, C
, C
33
13X
33X
53X
63X
, C
, C
)
*4
(10)3
(14)3
=1). Self-calibration takes
λ
, C
, C
83
83P
93
, C
83P
93
, C
, C
83X
93X

Hide quick links: