Superior Fireplaces WRT3036RS Installation And Operation Instruction Manual page 11

Table of Contents

Advertisement

Minimum Measurements
14
/
"
3
8
(48.3 cm)
1"
(2.54
cm)
1"
(2.54
cm)
Pitch
Slope
Flat
0-6/12
26.6°
6/12- 12/12 45.0°
Figure 14 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-8DM OR V12F-8DM)
Determine flashing to be used with roof opening chart. Slide flashing
over pipe until base is flat against roof. Replace as many shingles as
needed to cover exposed area and flashing base. Secure in position
by nailing through shingles (see Figure 15). DO NOT NAIL THROUGH
FLASHING CONE.
Installing Flashing on a Metal Roof
When installing flashing on a metal roof, it is required that putty tape
be used between flashing and roof. Flashing must be secured to roof
using #8 x 3/4" screws and then sealed with roof coating to prevent
leakage through screw holes. A roof coating must also be applied
around perimeter of flashing to provide a proper seal.
Storm Collar
Flashing
Cone
Nail Only Outer
Perimeter of
Flashing
Underlap Shingles
at Bottom
Figure 15 - Flashing Installation
126619-01D
VENTING INSTALLATION Continued
30"
(76.2 cm)
1"
(2.54 cm)
Opening "A"
Opening
Used Flashing
"A" Max.
Model No.
15"
V6F-8DM
16
/
"
V6F-8DM
1
8
20
/
"
V12F-8DM
3
8
Overlap
Shingles Top
and Sides Only
Superiorfireplaces.US.com
Storm Collar Installation (SC1)
Place storm collar over pipe and slide down until it is snug against
open edge of flashing (see Figure 16). Use SC1 for all round termina-
tions. Apply waterproof caulk around perimeter of collar to provide
a proper seal.
Chimney
Pipe
Storm
Collar
Figure 16 - Storm Collar
Terminations/Spark Arrestor
Fireplace system must be terminated with listed round top or chase
terminations. In any case, refer to installation instructions supplied
with termination. Terminations approved for this fireplace are RT-
8DM, RTL -8DM and RLT-8DM that can be used for flashing or chase
and ET-8DM, ETO-8DM, ETL-8DM and ETLO-8DM for chase style
termination only. Figure 18, page 12 shows an RTL-8DM round top
termination.
CAUTION: Do not seal openings on the rooftop
flashing. Follow the installation instructions provided
with the termination being used.
Terminations with 16" slip pipe sections are available. RTT-8DM,
RTTL-8DM and RLTT-8DM are approved for flashing installations.
When needed, these adjustable terminations may be used in combina-
tion with pipe assembly to achieve correct chimney height.
Note: In the rare instance there is a problem with side driven rain or
wind or chimney is not drafting properly, an ADS-8DM (Anti-Draft
Shield) can be used with round terminations.
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
Overlap
Shingles Top
and Sides
Figure 17 - Termination
Waterproof
Caulk
Flashing
RTL-8DM
Level of Flue
Gas Outlet
Flue Pipe of
RTL-8DM
Inside Inner
Pipe of
Chimney
Caulk
Collar
Flashing
Underlap Shingles
Bottom Only
11

Advertisement

Table of Contents
loading

Table of Contents