Installation Guidelines; What You'll Need; Items Included; Choose An Installation Location - Rinnai i060C Installation And Operation Manual

Wall-mounted, gas-fired combi boiler
Hide thumbs Also See for i060C:
Table of Contents

Advertisement

4
Topics in this section

Installation Guidelines

What You'll Need

Items Included

Choose an Installation Location

Mount the Boiler to the Wall

Fill the Condensate Collector

THIS SECTION IS INTENDED
FOR THE INSTALLER
Installer qualifications: A trained and qualified
professional must install the appliance,
inspect it, and leak test the boiler before use.
The warranty will be voided due to any
improper installation. The trained and
qualified professional should have skills such
as: Gas sizing; Connecting gas lines, water
lines, valves, and electricity; Knowledge of
applicable national, state, and local codes;
Installing venting through a wall or roof; and
training in installation of condensing boilers.
Training for Rinnai Condensing Boilers is
accessible online at
www.trainingevents.rinnai.us.
This boiler is certified for installation in
residential and commercial applications.
This boiler is suitable for combination
water heating and central heating.
The installation must conform with local
codes or, in the absence of local codes,
with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or the Natural Gas and
Propane Installation Code, CSA B149.1. If
installed in a manufactured home, the
installation must conform with the
Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280
and/or CAN/SCA Z240 MH Series, Mobile
Homes.
14
The appliance, when installed, must be
electrically grounded in accordance with
local codes or, in the absence of local
codes, with the National Electrical Code,
ANSI/NFPA 70, or the Canadian Electrical
Code, CSA C22.1.
The appliance and its main gas valve
must be disconnected from the gas
supply piping system during any
pressure testing of that system at test
pressures in excess of 1/2 psi (3.5 kPa)
(13.84 in W.C.). For system testing at
pressures less than or equal to 1/2 psi
(3.5 kPa) (13.84 in W.C.) the appliance
must be isolated from the gas supply
piping by closing its individual manual
shutoff valve.
You must follow the installation
instructions and those in section
"5. Venting" for adequate combustion
air and exhaust.
If this boiler's DHW system is connected
to a closed water supply system, such as
one having a backflow preventer in the
cold water supply line, means shall be
provided to control thermal expansion.
Contact the water supplier or local
plumbing inspector on how to control
thermal expansion.
Should overheating occur or the gas
supply fail to shut off, turn off the
manual gas control valve to the
appliance.
Combustion air must be free of
chemicals, such as chlorine or bleach,
that produce fumes. These fumes can
damage components and reduce the life
of your appliance.
Where required by the authority having
jurisdiction, the installation must comply
with the Standard for Controls and
Safety Devices for Automatically Fired
Boilers, ANSI/ASME CSD-1.
Rinnai I-Series Condensing Boiler Combi Manual