Outdoor Unit - Fujitsu AUXG07KVLA Service Manual

Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

6-2. Outdoor unit

¢ Discharge temperature thermistor
Temperature (°C)
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
6-2. Outdoor unit
Resistance (kΩ)
1,013.11
729.09
531.56
392.31
292.91
221.09
168.60
129.84
100.91
79.12
62.55
49.84
40.01
32.35
26.34
21.58
17.79
14.75
12.30
10.32
8.70
7.36
6.27
5.36
4.60
3.96
3.43
2.98
2.60
2.27
2.00
- (03-95) -
Voltage (V)
0.06
0.09
0.12
0.16
0.21
0.28
0.36
0.46
0.57
0.71
0.86
1.03
1.23
1.43
1.65
1.88
2.11
2.34
2.57
2.79
3.00
3.19
3.37
3.54
3.69
3.83
3.96
4.07
4.17
4.26
4.33
6. Thermistor resistance values

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents