2-35. E: 94. Over current error (Outdoor unit)

Indicator
Indoor unit
Detective actuator
Outdoor unit
Forecast of cause
Check point 1. Check connections of outdoor unit electrical components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
Check point 2. Check outdoor fan and heat exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of outdoor heat exchanger?
Is the fan rotating by hand when operation is off?
→ If the fan motor is locked, replace it.
Check point 3. Check outdoor fan
Check outdoor fan motor.
Refer to
"E: 97. Outdoor unit fan motor error (Outdoor unit)"
→ If the fan motor is failure, replace it.
2-35. E: 94. Over current error (Outdoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
Main PCB
Compressor
- (03-51) -
9 time flash
4 time flash
Continuous flash
E: 94
1. When more than normal operating current to IPM in
main PCB flows, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Defective connection of electrical components
Outdoor fan operation failure
Outdoor heat exchanger clogged
Compressor failure
Main PCB failure
on page 03-54.
2. Troubleshooting with error code